UA-5200 Series User Manual V4.3 ICP DAS
71
Convert Setting > MQTT > Modbus TCP (Master)
– Publish & Subscribe
Details
Click [Show] to display all fields, click [Hide] to hide some fields.
Name
The variable name of the mapping address.
(Not editable here)
Attribute
Display data attribute of the variable. (Not editable)
Include: Read, Read/Write
…
Data Type
Display data type of the variable
that set in the Modbus Address
Mapping Table page
. (Not editable) Include: Bool, Short, Float
…
Subscribe Topic
The topic of receiving/subscribing data message.
Subscribe Qos
The s
ubscribe
Qos (Quality of Service) levels. Default: 2
0: Delivering a message at most once.
1: Delivering a message at least once.
2: Delivering a message at exactly once.
Publish Topic
The topic of sending/publishing data message.
Publish Qos
The publish Qos (Quality of Service) levels. Default: 2
0: Delivering a message at most once.
1: Delivering a message at least once.
2: Delivering a message at exactly once.
Retain
Check [Retain] box of the top row can store the broker message
for all variables in list. Check the box of each variable can store
the broker message just that variable. Default: Uncheck.
Enabled
Check [Enabled] box of the top row can enable all variables in
list. Check the box of each variable can enable just that variable
for conversion. Default: Uncheck.
OK
Click to save this page settings and back to the module list page.
Содержание UA-5200 Series
Страница 13: ...UA 5200 Series User Manual V4 3 ICP DAS 13 1 5 Appearance UA 5231...
Страница 14: ...UA 5200 Series User Manual V4 3 ICP DAS 14 UA 5231M...
Страница 15: ...UA 5200 Series User Manual V4 3 ICP DAS 15 UA 5231M 3GWA 4GE 4GC...
Страница 225: ...UA 5200 Series User Manual V4 3 ICP DAS 225 The LINE APP messages received on the mobile phone...