UA-5200 Series User Manual V4.3 ICP DAS
139
Click [Edit] button to enter the
“Module Content Setting” page.
Module Content Setting
No.
The module number in the module list (Not editable here)
Module Name
Give a name, e.g. model number or name. Default: Name.
Slave ID
Set the module Slave ID of the UA-5200. (Range: 1 ~ 247)
Timeout
Set the timeout value for the module. Default: 500 ms
Modbus Mapping Table Setting
Data Model
System provides 4 Modbus data models
“01” ~ “04” for mapping to address of
DO, DI, AO and AI. (ex. 01: DO
channels, 02: DI, 03: AO, 04: AI)
Start Address
The start address of the Modbus command.
Note:
the address of UA
controller is start from 0, even if some modules are start from 1, here it
needs to set follow the UA series to start from 0.
Data Number
The number of the Modbus address. Need to give enough number for
the DO, DI, AO, AI channels of the module. Default: 1.
Type
This item only when the data model is 03 or 04. Choose the suitable
data type: 16-bit Short, 16-bit Unsigned Short, 32-bit Long, 32-bit
Unsigned Long, 32-bit Float, 64-bit Double.
Create Tables
Click [Add] button, it will add a table in the Modbus mapping table.