UA-5200 Series User Manual V4.3 ICP DAS
65
The finished Modbus Mapping Table as below is in order of DO, DI, AO and AI.
Modbus Mapping Table
– Address Setting
Address Setting
The
“Address Setting” page of the Modbus Mapping Table
Nickname
Setting
Click can switch to the The
“Nickname Setting” page of the
Modbus Mapping Table. (Next page)
Modbus
Mapping Table
Coil Status(0x): Mapping to DO Modbus address
Input Status(1x): Mapping to DI Modbus address
Holding Registers(4x): Mapping to AO Modbus address
Input Registers(3x): Mapping to AI Modbus address
Address
The start address of the Modbus command. Default: 0.
Note:
the
address of UA controller is start from 0, even if some modules are
start from 1, here it needs to follow the UA series to start from 0.
Number
The number of the Modbus address. Need to give enough number
for the DO, DI, AO, AI channels of the module. At least 1.
Type
DO/DI type: Bool (Boolean)
AO/AI type: depend on setting of [Modbus Mapping Table Setting]
Edit
Click to change the address and Number.
Delete
Click to delete this address table.
Save
Click to save and exit this table editing.
Cancel
Click to exit without saving and back to the module list page.
OK
Click to save this page settings and back to the module list page.
Содержание UA-5200 Series
Страница 13: ...UA 5200 Series User Manual V4 3 ICP DAS 13 1 5 Appearance UA 5231...
Страница 14: ...UA 5200 Series User Manual V4 3 ICP DAS 14 UA 5231M...
Страница 15: ...UA 5200 Series User Manual V4 3 ICP DAS 15 UA 5231M 3GWA 4GE 4GC...
Страница 225: ...UA 5200 Series User Manual V4 3 ICP DAS 225 The LINE APP messages received on the mobile phone...