background image

ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 

 

 

 

208 

Specify the variable from  the dropdown list  of  “Variable Name” 

field  that  you  are  going  to  include  it  in  the  IF  condition 

statements.

 

ii 

Set  up  the  expression  statement  for  the  content  of  this  Subscribe 

Topic. Select an operator from “=”, “>”, “=” or “<=”.

 

iii 

Specify  the  user-defined  evaluation  value.  If  the  content  of  this 

variable match the evaluation criteria, the result of this condition 
evaluation will be “true”. PMC/PMD provides 12 values options; 

you  can  compare  them  with  the  content  of  this  Subscribe  Topic 

for  condition  evaluation.  Please  refer  to  

11.1.1.2  DI  Counter

” 

section for more detailed information.

 

iv 

Click “OK” button to confirm the settings and return to the Rule 

settings page.

 

 

11.1.5

 

IBM Bluemix 

Click  on  IBM  Bluemix,  2  options  will  appear  as  the  following:  " 

Connection Status" and " Subscribe Message". 

 

11.1.5.1

 

Connection Status 

The  Connection  Status  between  PMC/PMD  and  IBM  Bluemix  can 

be used as evaluation criteria for IF condition statement. The editing 

page  for  IBM  Bluemix  Connection  Status  Condition  Setting  is 

shown as below: 

 

Figure11-13 :

 

IBM Bluemix Connection Status condition setting   

 

Follow the steps below: 

Specify  the  connection status  to  be “Offline” or  “Online”.  If the 

connection status of IBM Bluemix match the evaluation criteria, 
the result of this condition evaluation will be “true”.

 

ii

 

Click “OK” button to confirm the settings and return to the Rule 

settings page. 

 

11.1.5.2

 

Subscribe Message 

The  Command  and  Variable  in  the  Subscribe  Message  from  IBM 

Содержание PMD series

Страница 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 6 6...

Страница 2: ...close or terminate the communication mechanisms of their systems ICP DAS cannot guarantee that this controller is free of any actual or legal defects including but not limited to stability reliability...

Страница 3: ...17 5 1 2 Power Meter Statistics Information Overview 21 5 1 3 Other Information 22 5 1 4 I O Information 22 5 2 Power Data Information 23 5 2 1 Overview 23 5 2 2 Group Overview 24 5 3 Realtime Chart 2...

Страница 4: ...6 9 Rule File Import Export 78 7 Power Meter I O Module Setting 81 7 1 Power Meter Setting 82 7 1 1 Scan to add Modbus RTU Power Meters 83 7 1 2 Add Modbus RTU Power Meter Manually 84 7 1 3 Add Modbu...

Страница 5: ...8 9 The Format of User Defined Data File 143 9 IoT Platform Setting 144 9 1 Microsoft Azure Setting 145 9 2 IBM Bluemix Setting 149 9 3 MQTT Setting 151 9 3 1 Broker Setting 151 9 3 2 Topic Import Ex...

Страница 6: ...Status 214 11 1 14 Internal Register 214 11 1 15 PUE 215 11 1 16 Ping 216 11 2 THEN ELSE Action Setting 217 11 2 1 ICP DAS Module 218 11 2 2 Modbus Module 223 11 2 3 Power Meter 224 11 2 4 Microsoft...

Страница 7: ...ndix V The SNMP Variables for PMC PMD 320 Appendix VI The format of CGI Query command 328 Appendix VII Change the value of output channel of module or Internal Register by MQTT protocol 341 Appendix V...

Страница 8: ...e4 14 Power data Overview page 15 Figure4 15 Select the classification of Power data 15 Figure4 16 Display power data of the selected classification 16 Figure5 1 Information display options on Main Pa...

Страница 9: ...UE information Realtime 41 Figure5 34 PUE information History 1 42 Figure5 35 PUE information History 2 42 Figure5 36 I O Information login as Administrator 43 Figure5 37 I O Information login as Gene...

Страница 10: ...igure6 25 Group Setting 72 Figure6 26 Subgroup Setting 72 Figure6 27 Subgroup Setting Window 72 Figure6 28 Configurations for Subgroup 73 Figure6 29 Loops Phases of subgroup Setting 74 Figure6 30 Choo...

Страница 11: ...Board AO attribute setting page 100 Figure7 26 I O Module Setting Page 101 Figure7 27 The Scan button to search M 7000 DL module 102 Figure7 28 Set up the Scanning Range for the M 7000 DL module 102...

Страница 12: ...g Interface of IoT Platform 147 Figure9 4 Microsoft Azure Subscribe Topic setting page 148 Figure9 5 IBM Bluemix Setting page 149 Figure9 6 IBM Bluemix Subscribe Message setting page 150 Figure9 7 MQT...

Страница 13: ...1 Figure10 26 LINE Notify Chat Room Setting page 3 182 Figure10 27 LINE Notify Chat Room Setting page 4 182 Figure10 28 LINE Notify Chat Room Setting page 5 182 Figure10 29 Timer creating Page 184 Fig...

Страница 14: ...ition setting page 215 Figure11 25 PUE condition setting page 215 Figure11 26 Ping condition setting page 216 Figure11 27 DI Counter action setting page 218 Figure11 28 DO action setting page 219 Figu...

Страница 15: ...action setting page 234 Figure11 48 Re boot system Action setting page 234 Figure11 49 Reset modem action setting page 235 Figure11 50 Data Logger action setting page 235 Figure11 51 Rule Status actio...

Страница 16: ...llowing models Product Series PMC 523x PMC 224x Hardware Dimension 117 mm x 126 mm x 58 mm 33 mm x 160 mm x 129 mm Number of LAN Port LAN port x 1 LAN port x 2 LCD Detail Model Name PMC 5231 Series PM...

Страница 17: ...ave modules By working with the I O modules and functions such as IF THEN ELSE logic rule execution and LINE Notify Email SMS Alarm Notification PMC 523x PMC 224x PMD offers more thought out power dem...

Страница 18: ...ution for power management and monitoring that makes more efficient energy usage PMC PMD features Web Based Operation No extra software tool is required all operations can be done through the Web brow...

Страница 19: ...nnect with power meters collect and transfer the power data to the Cloud platform for future data analysis PMC 523x PMC 224x PMD also can receive the message which is published from the Cloud platform...

Страница 20: ...ult of the formula and save the result into the Internal Register for IF THEN ELSE rule checking or data logging Offers access management for logic rule settings and encoded function for the content t...

Страница 21: ...web page go to System Setting Network Setting modify the network setting to fit current network environment More detailed setting information please refer to 6 2 Network Setting 6 Save the settings a...

Страница 22: ...allows performing Logic rule edition Only one administrator is allowed to login into the system at the same time General User Default password User General users are allowed to view power meter data a...

Страница 23: ...page will be displayed and will automatically read settings of the PMC PMD to the webpage Figure4 1 Main Page PMC PMD main page could be divided into 3 areas A System function area B Sub function area...

Страница 24: ...user the setting functions in Rules management toolbar and System function toolbar will be locked and only allows viewing the power meter data the I O module data and Real time system information The...

Страница 25: ...eared If the user would like to clear the setting on PMC PMD then continue to click on Save button to save the new settings cleared settings to the PMC PMD Please note once the settings are cleared an...

Страница 26: ...r as below Figure4 10 Confirm to logout The settings are not saved Please note 1 All the edited settings on the webpage have to be saved to PMC PMD to make all settings take effect before click on but...

Страница 27: ...s available to save of the micro SD card in PMC PMD Allows display of real time system information click on Instant Message to open up the list of real time information maximum 10 information will be...

Страница 28: ...Series User Manual 13 Chapter 11 Rule Setting If login as a general user they are allowed to view real time information on Main Page only they also do not have the permission to edit the settings of...

Страница 29: ...isplayed to show the current function path Figure4 13 Current function path 4 3 Data review System setting area Data review System setting area allows to set system parameters and data review of PMC P...

Страница 30: ...data immediately The power data classification includes the following options V Voltage I Current kW Real Power kvar Reactive Power kVA Apparent Power PF Power Factor kWh kvarh kVAh Daily Accumulated...

Страница 31: ...ries User Manual 16 Figure4 16 Display power data of the selected classification Connection Status will reveal the connection status between the power meter and PMC PMD the graphic indicators are as f...

Страница 32: ...able Information and UID information shown as follow Figure5 1 Information display options on Main Page 5 1 Power Meter Information Power Meter Information page displays detailed power data informatio...

Страница 33: ...er Attribute The Power Meter Attribute section will display different information according to different power meters and the ways they are connected to the PMC PMD Currently PMC PMD supports connecti...

Страница 34: ...es real time power data information of the selected Power Meter For 3 phase power meter it will display real time information of Phase A Phase B and Phase C Figure 5 5 For single phase power meter it...

Страница 35: ...n of PM 3112 Reset Accumulated Value of the Power Meter When login as the Administrator it allows to click on Reset to reset the value of kWh kvarh and kVAh to be 0 if required Please Note After perfo...

Страница 36: ...and and Monthly Maximum Demand etc In the Statistics Information section the Daily Monthly Yearly Accumulated Electricity and Daily Monthly Yearly Carbon Emissions for each loop will be displayed Figu...

Страница 37: ...fic parameters of the power meter Figure5 9 Power Meter Other Information Page 5 1 4 I O Information In the I O information page the I O status of the power meter will be listed When login as the Admi...

Страница 38: ...ification from the dropdown list of the Data Classification field it will list the requested data from various power meters for easy comparison The page refreshes every 20 seconds the user could also...

Страница 39: ...5 2 2 Group Overview Power Data Information group overview mode allows display of power data of pre set group of power meters please refer to 6 7 Power Meter Group Setting The page refreshes every 20...

Страница 40: ...splayed power data will be varied according to the selected power data classification 5 3 Realtime Chart Realtime Chart allows display of power information of the power meter in real time trend and pi...

Страница 41: ...cally The user could choose desired power data classification to view the corresponding Realtime Chart The chart refreshes every 5 seconds Figure5 15 Realtime Chart Power Meter Mode There are three fu...

Страница 42: ...sponding subgroups will be listed If the selected Group contains no subgroup or the subgroup doesn t setup any loop phase of the power meter the inquiry operation will not be able to perform Data Clas...

Страница 43: ...ed The user could click and drag on the chart and move forward or backward to show desired time zone Click to resume the update of the chart To view the data on a specific marker move the mouse over t...

Страница 44: ...own list of the Power Meter List if no power meter is connected the inquiry operation will not be able to perform Data Classification Data Classification allows to inquire various power data options i...

Страница 45: ...marker the value will be displayed Figure5 18 Historical Data Chart for power data On the upper left of the Historical Chart there are 4 function icons Set the Historical Chart to be default status Z...

Страница 46: ...e Go to next page Go to last page 5 5 Historical Data Report The Historical Data Report allows display of the power data report of desired power meter specify the power meter power classification and...

Страница 47: ...eport Monthly Report or Annual Report options Report Date The dates that are available for data retrieval will be displayed Please note if no log file is available the inquiry operation will not be pe...

Страница 48: ...s by Time and Energy Usage Breakdown by Circuit Group The user can query electricity analysis for specific date by selecting Chart Type Data Classification Date and Loop s Phase s the following sectio...

Страница 49: ...Energy Usage KWh Carbon Emissions and Maximum Demand Chart Type Provides Yearly Chart Monthly Chart and Daily Chart Date Select the date range to be queried the system will provide the date range can...

Страница 50: ...ser defined Mode Click on Inquiry button to display the trend of Energy Usage Analysis for the specified date range If the selected date does not contain the file or exceeds the date of the file stora...

Страница 51: ...ut the Y axis of the Energy Usage Analysis by Trend Chart Hide the markers on the Energy Usage Analysis by Trend Chart Show the markers on the Energy Usage Analysis by Trend Chart 5 6 2 Energy Usage A...

Страница 52: ...includes V voltage I current PF power factor Energy Usage KWh Carbon Emissions and Maximum Demand Chart Type Provides Yearly Chart Quarterly Chart and Monthly Chart Date Select the date range to be qu...

Страница 53: ...ta classification and the time range under this section and then select the loop s phase s to be inquired the corresponding Energy Usage Breakdown by Circuit Group will be displayed in category pie ch...

Страница 54: ...m inquiry operation Figure5 31 Inquiry by Group Mode User defined In user defined mode all power meters connected to the PMC PMD will be listed If no power meter is connected the user will not be able...

Страница 55: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 40 the table Figure5 32 Energy Usage Breakdown by Circuit Group Chart...

Страница 56: ...lues which are calculated by Total Facility Energy and IT Equipment Energy preset by users The page refreshes every 20 seconds the user could also click Refresh button to refresh the data immediately...

Страница 57: ...Provides Daily Chart and Monthly Chart Date The dates which are available for PUE data retrieval will be displayed Please note if no log file is available the inquiry operation will not be performed...

Страница 58: ...he PMC PMD If login as the Administrator it allows to modify the values of Internal Registers or output values of the DO AO channels Figure 5 36 If login as a general user they are allowed to view the...

Страница 59: ...Chart There are three function icons on the upper area of the I O Realtime Chart The icon allows to pause the update of the chart only the data within the 25 minutes will be displayed The user could...

Страница 60: ...ield select the I O channel from the Channel Selector field then click on Inquiry button it will show the chart The interface is shown as below User also can click the Download CSV button to download...

Страница 61: ...t be able to perform Click on Inquiry to display the channel data historical statistic chart Figure 5 40 of the selected date If the selected date does not contain the file or exceeds the date of the...

Страница 62: ...ollowing information The PMC PMD failed to read data of the power meter s Change the network settings on the PMC PMD Save settings to the PMC PMD Change the system time setting Reset accumulated power...

Страница 63: ...ing Time Information The graphic indicator on the right side of the No will reveal the connection status of the module the graphic indicators are as follow Online Offline Connecting 5 13 Modbus Table...

Страница 64: ...module name or information of Module Name will be listed Click on Inquiry to display the Modbus table information of the selected module The users can click on the Print button to print this Modbus ad...

Страница 65: ...e latest Ping results of all Ping targets The latest ping result is displayed in the Result column and the response time is displayed in the Response Time column In the Failed Times Ratio column it di...

Страница 66: ...options Time Setting Network Setting SNMP Setting Security Setting I O Interface Setting Power Meter Group Setting and Other Setting When you get into the System Setting page the system settings infor...

Страница 67: ...etting Page When get into this page the system will read and display current time of the PMC PMD To modify the system time of PMC PMD set up the date and time on the Time Setting page section and then...

Страница 68: ...Servers to restore the default Time Server settings iii The default Port number setting is 123 currently it is not allowed to be modified iv In the Sync Interval field select the time interval to spec...

Страница 69: ...work configuration web server port setting Modbus settings Dynamic DNS setting and IoTstar Connection settging on the PMC PMD The following figure illustrates the configuration interface Please Note P...

Страница 70: ...b page automatically based on the new setting If the connection mode is Obtain an IP address automatically DHCP the system may fail to re connect to the web page because the IP address is changed Plea...

Страница 71: ...etting Page and the connection status Connect or Disconnect can be changed manually This section also displays the strength level of the Mobile Network Signal and the IP address that PMC 5231M 4GE or...

Страница 72: ...ect Disable to disable the service iii If user selects No IP ChangeIP Dyn or DNS O Matic please enter the ID Password and Domain Name to login the service If user selects Free DNS please insert the To...

Страница 73: ...ection If user select User built IoTstar please click in the Server Address field then input the IP address or Domain Name of the PC or Platform with IoTstar installed Enter the login username and pas...

Страница 74: ...cation Figure6 8 IoTstar connection setting page 1 iv After all settings are completed click Save button to save the changes This PMC PMD will connect to the IoTstar immediately The users can review t...

Страница 75: ...the set up interface Figure6 9 SNMP Setting Page Please follow the steps below for the SNMP Settings i In the Version field select the SNMP version that you want to use Currently PMC PMD supports SNMP...

Страница 76: ...e changes Figure6 10 SNMP Manager List i Set up IP Address or domain name of the SNMP Manager that you want to add Please set up the Address appropriately if the settings are not the same as the setti...

Страница 77: ...Write commands indicating that it will allow accepting the Read Write commands from ANY SNMP Manager iii After completing the IP address and working model setting please click button to add the SNMP...

Страница 78: ...etting Page Password Setting PMC PMD provides two passwords sets one for Administrator the other for Guest The default password for Administrator is Admin and User for Guest The user can modify the pa...

Страница 79: ...tting Page Local FTP Server Setting In this section it allows to enable or disable the FTP Server function on the PMC PMD side The user could connect to PMC PMD FTP Server via FTP software to remotely...

Страница 80: ...LAN of PMC PMD The setting interface is shown as below Figure6 18 I O Interface Setting Page The I O interface functions for PMC PMD are as below Model I O interface function PMC 523x PMC 224x COM2 R...

Страница 81: ...odbus TCP Slave to connect HMI or SCADA It can also be set for Modbus TCP Mater to connect Modbus TCP devices The following section will introduce how to set I O interface for different functions Conn...

Страница 82: ...commands from the PMC PMD to the Modbus RTU slave device the unit will be millisecond ms Please Note After the Baudrate is selected the system will automatically generate a proper value in the Silent...

Страница 83: ...ault set for Modbus TCP Slave to connect HMI or SCADA User can also select the Modbus TCP Master Checkbox to enable the Modbus TCP Mater function for connecting to Modbus TCP Slave devices through Eth...

Страница 84: ...ty being set will be displayed on the System Setting main page Demand Interval Setting In this section it allows to set Demand Interval Setting The system will calculate the demand according to this d...

Страница 85: ...electricity carbon emissions if user does not complete the carbon emission factor setting for the corresponding year the system will use the value in the Default Factor field for calculation iii Clic...

Страница 86: ...istorical Electricity Analysis pages for power data analysis The power meter group setting page is shown as below Figure6 23 Power Meter Group Setting Please refer to the following chapters to setup t...

Страница 87: ...User Manual 72 Figure6 25 Group Setting Figure6 26 Subgroup Setting ii Input the group subgroup name and click to add this group subgroup to the lists Click Close button to return to group setting pag...

Страница 88: ...Move Up to move the group to upper order upper index number No Move Down Click the radio button in front of the group and click on Move Down to move the group to lower order lower index number No Cop...

Страница 89: ...r Manual 74 Figure6 29 Loops Phases of subgroup Setting ii Select the loop phase of the power meter and click to add this loop phase to the lists Click Close button to return to group setting page Fig...

Страница 90: ...click on the function button to perform the configurations Move Up Click the radio button in front of the loop phase name and click on Move Up to move the loop phase to upper order upper index number...

Страница 91: ...ia browser after the update is completed the PMC PMD doesn t require to reboot Please follow the steps below i Please contact ICP DAS service to obtain the latest version of the PMC PMD firmware file...

Страница 92: ...through to select the new firmware file and click Open Figure6 34 Firmware Update 2 iv Click Update to update the firmware Figure6 35 Firmware Update 3 v Click OK to start the firmware update to cance...

Страница 93: ...the update process is failed please perform the update again Figure6 38 Firmware Update 6 6 9 Rule File Import Export PMC PMD can directly perform the PMC PMD s Rule file import and export operations...

Страница 94: ...MC PMD s Rule file 1 After click the Export Settings button the rule file would be stored in the default download path according to the browser s setting If there was setting of PMC PMD has not been s...

Страница 95: ...er will be asked whether to abandon the current settings or not If user select Import the current settings of PMC PMD will be cleared after the import operation 3 After the import process is done PMC...

Страница 96: ...eters and I O Modules that are connected to the PMC PMD After getting into the setting page the overview page will display current setting of the power meters and I O Modules that are connected to the...

Страница 97: ...s RTU and Modbus TCP power meters After all settings are completed click Save button to save the changes Please note 1 PMC PMD provides 2 COM Port RS 485 interface that allows connections to Modbus RT...

Страница 98: ...ters that are connected to the PMC PMD Figure7 3 The Scan button to search Power Meter iii When the Scan page appears Figure 7 4 input the starting address and the ending address of the Modbus address...

Страница 99: ...re 7 7 please select the actual device that are connected to PMC PMD After all settings are completed click Save button to save the changes Figure7 6 The Power Meter List after Scan operation Figure7...

Страница 100: ...odule if the setting is not accurate the connection for PMC PMD to the power meter will be failed Figure7 8 Set up the No and Address of the power meter iii Select the Power meter model Figure7 9 Sele...

Страница 101: ...umber will be the order that the power data of the Modbus TCP power meter being stored in the PMC PMD Modbus Table The range is 1 16 ii Network Set up the settings of IP Port and NetID appropriately a...

Страница 102: ...ter manually 7 1 4 Power Meter List Interface After the Modbus RTU TCP Power Meters are added to the power meter list via auto scan or manual work the Modbus RTU TCP Power Meters will be listed as bel...

Страница 103: ...he pre set power meter and then click on Copy a new power meter in sequence will be added to the list and the settings of the old power meter will be copied to this newly added power meter Remove Clic...

Страница 104: ...the same as the settings of the module if the setting is not accurate the connection for PMC PMD to the power meter will be failed Scan Rate Input the time interval for PMC PMD to periodically retriev...

Страница 105: ...ll be displayed on the Power Meter Information and Rule Setting pages For three phase power meter the user could give nicknames to the Phase A B C After all settings are completed click OK button to r...

Страница 106: ...for each DO channel this nickname will be displayed on the Power Meter Information and Rule Setting pages Power On Value Set up the initial value for the DO channels when the power meter is powered on...

Страница 107: ...module if the setting is not accurate the connection for PMC PMD to the power meter will be failed Scan Rate Input the time interval for PMC PMD to periodically retrieve the power data of this Modbus...

Страница 108: ...ine nicknames for each DO channel this nickname will be displayed on the Power Meter Information and Rule Setting pages Power On Value Set up the initial value for the DO channels when the power meter...

Страница 109: ...ick Setting a window for setting up the parameters of XV Board and its I O channel will appear The setting for the module is shown as below Nickname For user to define a nickname for the module this n...

Страница 110: ...cates that the counter of this DI channel will not function Counter Initial Value Set the initial value of the counter in the Counter Initial Value field This counter will start counting from the init...

Страница 111: ...e dropdown list Pulse Output If the Pulse Output is selected it will allow this DO channel to perform pulse output and form a periodic pulse cycle In Pulse Output mode the selected DO channel will gen...

Страница 112: ...e channels are completed click OK button to return to XV Board Setting page 7 2 3 XV Board AI Channel Settings The XV Board AI Channel Setting page is shown as follow using PMC 5231 XV310 as an exampl...

Страница 113: ...ere are three operation styles for AI Deadband The AI Channel setting in following examples is 0mA 20mA a In the IF Condition when AI or a numerical value Assuming the Deadband value is set to be 2 mA...

Страница 114: ...23 AI Deadband Operation or a numerical value c In the IF Condition when AI a numerical value Assuming the Deadband value is set to be 1 mA and the following statements are defined in the related log...

Страница 115: ...Board AO attribute setting page The settings are as follow Nickname For user to define nicknames for each I O channel this nickname will be displayed on the I O Information and Rule Setting pages Type...

Страница 116: ...he 2 COM Port RS 485 interfaces on PMC PMD allows connections to Modbus RTU I O modules 2 The LAN interface on PMC PMD allows connections to Modbus TCP I O modules For more detailed information of the...

Страница 117: ...dule ii When the Scan page appears Figure 7 28 input the starting address and the ending address of the Modbus address that are going to perform scan Click on Scan the system will start to scan the M...

Страница 118: ...7 30 If the newly scanted module doesn t match the module previously set on the same address a window will appear Figure 7 31 please select the actual device that are connected to PMC PMD After all s...

Страница 119: ...this Modbus RTU module please make sure the address is the same as the settings of the module if the setting is not accurate the connection for PMC PMD to the Modbus RTU module will be failed Figure7...

Страница 120: ...anually add Modbus TCP modules please follow the steps below i No The number will be the order that the I O channel data of the Modbus TCP module being stored in the PMC PMD Modbus Table The range is...

Страница 121: ...nd click on the function button to perform the operations Setting Click the radio button in front of the Modbus I O module and click on Setting to get into the setting page of the Modbus I O module Th...

Страница 122: ...I O Information and Rule Setting pages Description The Description field provides a space for the user to make a brief description of this M 7000 DL module Address The address will be the Modbus addr...

Страница 123: ...r to define nickname for each I O channel this nickname will be displayed on the I O Information and Rule Setting pages Reset counter when power on If the Reset counter when power on is selected for t...

Страница 124: ...The settings are as below Nickname For user to define nickname for each I O channel this nickname will be displayed on the I O Information and Rule Setting pages For M 7000 DL DO channels PMC PMD prov...

Страница 125: ...status is OFF DO0 will set to be OFF as well After all settings are completed click OK button to save the changes and return to Modbus RTU Module List Please Note 1 To set up the Power On value of th...

Страница 126: ...tion and Rule Setting pages Type Select the input signal type of the AI channel from the dropdown list Deadband Please refer to Deadband section in the 7 2 3 XV Board AI Channel Settings for more deta...

Страница 127: ...pe of the AO channel from the dropdown list After all settings are completed click OK button to save the changes and return to Modbus RTU Module List Please note To set up the Power On value of the AO...

Страница 128: ...is nickname will be displayed on the I O Information and Rule Setting pages Description The Description field provides a space for the user to make a brief description of this module Address The addre...

Страница 129: ...te Input Input Register and Holding Register configurations on Modbus RTU Slave module Please Note The number of Modbus address setting blocks will affect the data update rate for the Modbus RTU Slave...

Страница 130: ...address block will be added to the Modbus address mapping table All added address blocks will be located in sequences staring from the Starting Address of the Coil Output The address number on the fir...

Страница 131: ...ame for the address blocks the user can click on the Nickname Setting tab and then input the Nickname for each address block The Nickname will be shown in the I O Information and Rule Setting pages Af...

Страница 132: ...ress and Data Number setting click on Add button A new Discrete Input address block will be added to the Modbus address mapping table All added address blocks will be located in sequences staring from...

Страница 133: ...to assign a Nickname for the address blocks the user can click on the Nickname Setting tab and then input the Nickname for each address block The Nickname will be shown in the I O Information and Rul...

Страница 134: ...er finishing the Start Address setting specify the Data Number it is the number of Input Register data you would like to retrieve from the Start Address Type The system support 6 kinds of data type se...

Страница 135: ...in sequences staring from the Starting Address The address number on the first column of the Local Address indicates the local Modbus address of PMC PMD to keep the Input Register data Figure 7 48 sho...

Страница 136: ...Transformed Value will be saved in floating point format on the PMC PMD no matter what format the raw Input Register value was in the device The default Scale Ratio will be 1 and the default Offset is...

Страница 137: ...Data Model selections to match the Modbus RTU Slave module configuration Please refer to the above section The Coil Output Setting of Modbus RTU Module for detailed information In this case please sel...

Страница 138: ...g Endian will appear Enable Inverse Big Endian to receive the data in big endian format correctly After finishing the Start Address Data Number and Type setting click on Add button A new Holding Regis...

Страница 139: ...e section The Input Register Setting of Modbus RTU Module If the user wants to assign a Nickname for the address blocks the user can click on the Nickname Setting tab and then input the Nickname for e...

Страница 140: ...ormation and Rule Setting pages Description The Description field provides a space for the user to make a brief description of this module IP Allows modification of the IP address of this Modbus TCP S...

Страница 141: ...The time interval to wait for PMC PMD to repeatedly send command again when PMC PMD sends command to the Modbus TCP module and get no response The unit will be second The setting range will be 3 6553...

Страница 142: ...ng options from power data I O channel data or Internal Register data The data log files of these two data loggers are both in CSV format that enables easy integration with the backend database system...

Страница 143: ...PMC PMD the I O Data Logger allows recording all the data of the I O modules that are connected to the PMC PMD and the User Defined Data Logger allows recording user defined data such as power data I...

Страница 144: ...he Column Header at the beginning of the data logger file to specify the name of the data iv Set the language of Excel format file of the report from the dropdown list of the Reports If Disable is sel...

Страница 145: ...CT1 V for user to check if the setting is appropriate please refer to the figure as below viii In the Log Interval field select from the dropdown list to set the time interval of the recording sessio...

Страница 146: ...fined Data Logger then PMC PMD will delete some old log files to keeps the data logger operation work continuously 8 2 Event Logger Setting The Event Logger allows to record system event of the PMC PM...

Страница 147: ...input Address Port ID Password and Path iii The user could test if the FTP settings are correct in the Remote FTP Server Setting Test section After clicking Send the system will create a folder on the...

Страница 148: ...ncy can be set as once a day once a week or once a month vi After all settings are completed click Save button to save the changes Please Note 1 All data logger files of PMC PMD will be saved in the m...

Страница 149: ...the Advanced Setting Email Setting section then the Receiver Email Address will automatically import the recipient list from the information of the Email you select ii In the Compressed File field ver...

Страница 150: ...st from the information of the Email you select ii In the Compressed File field verify if the attachment report file of the email have to be compressed or not iii In the Report Type field select the r...

Страница 151: ...ily Report Log 01A3851F140000D3_2 3133 7 2013 05 23Rpt csv Monthly Report Log 01A3851F140000D3_2 3133 7 2013 05Rpt csv 01A3851F140000D3_2 3133 7 is the ID of this power meter 01A3851F140000D3 indicate...

Страница 152: ...ord the nickname of the power meter and the related information of the PMC PMD which connect to the power meter The I O Data Log file is also saved under the Log file folder the data file architecture...

Страница 153: ...ltage Current kW kvar kVA PF kWh kvarh kVAh Daily tot Electricity kWh Current demand 15 30 60 mins Reserved Field PM 2134 PM 3112 MTCP PM 3114 MTCP Data Logger Field Date Time Power meter ID CT1 Volta...

Страница 154: ...h kVAh Daily tot Electricity kWh Current demand 15 30 60 mins Reserved Field 8 7 The format of the Power Report file The power report files are saved in CSV format Each line represents one record each...

Страница 155: ...ming of daily max kW daily max kW daily total Electricity Average daily PF Average daily current Average daily voltage Average daily kVA Average daily kvar Reserved Field PM 4324 MTCP PM 4324A MTCP Da...

Страница 156: ...M 4324 MTCP PM 4324A MTCP Monthly Report Date Time Power meter ID Submeter 1 CT1 Timing of daily max kW daily max kW daily total Electricity Average daily PF Average daily current Average daily voltag...

Страница 157: ...iming of daily max kW daily max kW daily total Electricity Average daily PF Average daily current Average daily voltage Average daily kVA Average daily kvar CT24 Timing of daily max kW daily max kW da...

Страница 158: ...data according to the data format and content set by the user In addition the system will tag each data log with information such as date time and type of the data etc The log type could be Period Rec...

Страница 159: ...With the IoT Platform Setting function the PMC PMD provides it helps users to implement an IoT system in a easy way In additional PMC PMD supports to connect to the IoT cloud management software IoTs...

Страница 160: ...the Documentation Azure IoT Hub IoT Hub MQTT support section on the Microsoft Azure Web Site for detailed information iii The value in keep alive Time field defines the maximum amount of time in secon...

Страница 161: ...Publish Message User can click on Add new Publish Message to add a new Publish Message Figure9 2 Microsoft Azure Publish Message setting page viii Input a name in the Nickname field and you could als...

Страница 162: ...rface of IoT Platform x The timing to publish message is set in the Auto Publish field there are two options When the I O data changed and the variation exceeds xxx and Periodical Publish If the When...

Страница 163: ...message the PMC PMD receives Target door Action open Timestamp 2016 10 17 15 17 22 In this example the Target and Action variable setting will be performed first Each time when the PMC PMD receives th...

Страница 164: ...ow i Check Enable in the Function Status field to enable the connection to IBM Bluemix IoT Cloud Platform ii In the Organization ID Device Type Device ID and Device Authentication Token fields input t...

Страница 165: ...n status to verify the setting is correct or not vi The lower half section on the IBM Bluemix Setting Page is for the Publish Message and Subscribe Message setting User can click the tab of Publish or...

Страница 166: ...ton to save the settings After downloading the settings to the PMC PMD the PMC PMD will initiate the connection to IBM Bluemix and start the Publish Message Subscribe Message mechanism with IBM Bluemi...

Страница 167: ...d the new MQTT Broker After clicking the Add new MQTT Broker the MQTT Broker Setting Page will appear The upper half area of the setting page is about the Broker parameters setting It will be shown as...

Страница 168: ...encryption mechanism is required for the connection between the Broker and the PMC PMD via MQTT click the Enable checkbox of the Encryption field to enable this function x The value in keep alive Tim...

Страница 169: ...be the model name of the PMC PMD If there are more than one PMC PMD controllers in a system for MQTT connection please remember to change the Topic Prefix setting to distinguish the Publish Topic Subs...

Страница 170: ...alue of the module will be bound with the Publish Message If user select All channels it mean all power data and I O channel values of the module will be added in the Publish Message List If the user...

Страница 171: ...the variation exceeds xxx and Periodical Publish If the When the I O channel data changed and the variation exceeds xxx is selected the system will automatically publish the topic when the power data...

Страница 172: ...c It allows user to change the value of the Internal Register and the value of the output channel of I O module or power meter by MQTT protocol Please refer to Appendix VI for detailed information xxv...

Страница 173: ...T Topic To use the Topic Import function please prepare a document with the same format as The_nickname_of_Topic Topic message Click the Import Topic button then browse through to select the document...

Страница 174: ...of MQTT Topic 9 4 IoTstar Real Time Data Sending Setting IoTstar can receive the real time power data and I O data uploaded by PMC PMD and import these data into the database it created The setting pa...

Страница 175: ...ame of the power data or I O channel data in the Name field To remove a pre set power meter loop or I O channel please click the radio button in front of the pre set power meter loop or I O channel an...

Страница 176: ...v3 3 0 and later version firmware of PMC PMD supports the message sending function to IoTstar Bot When PMC PMD is set to connect to an IoTstar server and the IoTstar server enables IoTstar Bot functi...

Страница 177: ...Internal Register value into the messages To make it easy to add the encoded string PMC PMD provides Real time variable editor Please refer to 8 1 Data Logger Setting for more detailed information of...

Страница 178: ...ting page Please note In order to avoid possible error when performing rule definition IF THEN ELSE please always finish configuration in Advanced Setting before starting to define Rules Avoid unneces...

Страница 179: ...ield shown as below Figure10 2 Email setting page Name Description iii In the SMTP Server field enter the IP or the domain name of the SMTP server or select the SMTP server from the dropdown list In t...

Страница 180: ...sword field viii In the Security field select the security setting to be No Security TLS or SSL from the dropdown list ix After complete SMTP server setting continue to input Email address setting In...

Страница 181: ...detailed information of the Real time variable editor xiv Click on OK to confirm the setting and leave the setting page xv Repeat steps i xv to complete settings of all Emails To modify the settings o...

Страница 182: ...e 2 types of SMS commands Retrieve channel data GET The user can retrieve specific channel real time data One SMS Command message can require up to 10 channel data values The user could add the encode...

Страница 183: ...Unicode mode is adopted the length of the content cannot exceed 70 characters If the Unicode mode is not selected will support English characters only the length of the content limit is 160 character...

Страница 184: ...the pre set SMS Alarm and then click Remove xii After you finish all the SMS Alarm selections and settings click Save button to save the settings 10 2 2 SMS Command Setting The SMS Command Setting pa...

Страница 185: ...itor section In the Command String Editor section select the command type to be GET retrieve real time channel data or SET modify channel data from the dropdown list For GET command shown as Figure 10...

Страница 186: ...and Setting for SET Command vii Click on OK to confirm the setting and leave the setting page viii Repeat steps v vii to complete settings of all SMS Command setting The SMS Command and its original c...

Страница 187: ...when user send SMS message DO to PMC 5231 3GWA PMC 5231 3GWA will set the value of DO0 on XV Board to be ON after receiving the message ix To modify the settings of a pre set SMS Command please click...

Страница 188: ...NMP Trap setting is shown as below Figure10 12 SNMP Trap Setting Page The settings steps are as below i Input Nickname and Specific ID and then click button to create a new SNMP Trap ii To modify the...

Страница 189: ...nnel Data type The setting page interface will be shown as below Figure10 14 Channel Data Type Setting Page Based on the Channel Data type interface it provides the encoded string for user to easily a...

Страница 190: ...low Figure10 16 User Defined Data Type Setting Page Set up the content in the User Defined Data field of the SNMP Trap Variable Binding Setting Page The User Defined Data provides encoded strings for...

Страница 191: ...n editing the content the user can select the View tab and then the channel encoded string will be displayed in the real index format of the channel for user to check the settings in an easy way The f...

Страница 192: ...bindings setting and return to the SNMP Trap Setting Page Figure10 19 SNMP Trap setting with variable bindings list viii To copy the settings of a pre set SNMP Trap to the new SNMP Trap please click t...

Страница 193: ...ge users have to apply a LINE Notify service first and connect the service with the personal account or chat room to be sent Please refer to the LINE Notify guide webpage on PMMS official webpage for...

Страница 194: ...d iv Enter the message content in the Content field LINE message provides an encoded string for you to add current power data I O channel data or Internal Register data into LINE messages To make it e...

Страница 195: ...Figure10 23 LINE Notify Message Setting page 4 vi After complete all settings click the OK button to confirm the LINE Notify message setting and return to the Message Setting page vii Repeat steps ii...

Страница 196: ...applied service and click the Send button the LINE login interface will appear if the client data was correct If you do not apply the service before click the link of No Client ID and Client Secret at...

Страница 197: ...t this account one to one or a group under this account which PMC PMD will connect to Figure10 27 LINE Notify Chat Room Setting page 4 iv After the connection procedure is complete the new chat room w...

Страница 198: ...join the group to receive the messages from PMC PMD 10 5 Timer Setting PMC PMD provides Timer for timing functions The Timer status can be Not Timeout or Timeout They can be included in the IF Condit...

Страница 199: ...Please refer to ch 10 8 Internal Register Setting to setup internal register iv Click button to create a new Timer Figure10 29 Timer creating Page v Repeat steps i iv to complete settings of all Timer...

Страница 200: ...ase click the radio button in front of the pre set Timer and then click Remove ix After all timer settings are completed click Save button to save the changes 10 6 Schedule Setting PMC PMD provides Sc...

Страница 201: ...n the Date section the calendars corresponding to the Year and Month you specified will appear as shown below Figure10 33 Calendar mode of Schedule setting b In the Time Range s section click Add to a...

Страница 202: ...be In Range that is during the date range you select the operation will be executed every day Select All button is used to set all dates to be In Range whereas Unselect All button is for marking all d...

Страница 203: ...set one day after the start date Click Remove to remove a pre set Time Range iv Click on OK to confirm the setting and leave the setting page v Repeat steps i iv to complete settings of all Schedule v...

Страница 204: ...cription field iii Setup the calculation expressions of the Total Facility Energy and users can click add button to modify the expressions iv Setup the calculation expressions of the IT Equipment Ener...

Страница 205: ...the PUE and then click on Setting to modify the settings xiiTo copy the settings of a pre set PUE to the new PUE please click the radio button in front of the pre set PUE and then click Copy a new PUE...

Страница 206: ...al PMC PMD supports math formula editing function with the firmware v3 3 0 or later version for the Internal Registers Users can edit different formula in each Internal Register by assing the power da...

Страница 207: ...user want to edit the formula for Internal Register please check Enable in the Function Status field of the Formula Setting section Figure10 38 Internal Register setting page 2 iii Edit math formula i...

Страница 208: ...settings vii To copy the settings of a pre set internal register to the new internal register please click the radio button in front of the pre set internal register and then click Copy a new interna...

Страница 209: ...ent method to check the Ping IF condition If you select Continuous ping failed up to X times you can set the continuous failed times with a number between 1 to 60 The Ping status would become failure...

Страница 210: ...face will also be shown on the left side of the page Detailed description is as below Add new rule To add a new rule please click Add new rule Copy To copy the settings of an old rule to the new rule...

Страница 211: ...THEN ELSE Action setting click on Save to save the settings Please note if you make modification in Power meter setting IO module setting or in Advanced Setting after finish defining the rules it migh...

Страница 212: ...uld click on and drag the component to arrange the components into appropriate order The following section will give more detailed information of IF Condition and THEN ELSE Action settings 11 1 IF Con...

Страница 213: ...e as follow 11 1 1 ICP DAS Module Click on ICP DAS Module XV Board M 7000 DL 3 options will appear as the following DI DI Counter and AI 11 1 1 1 DI DI channel value from XV Board M 7000 module can be...

Страница 214: ...expression statement for this counter value Select an operator from or Change iii And then specify the evaluation value If this DI Counter value match the evaluation criteria the result of this condit...

Страница 215: ...other ICP DAS modules such as XV Board M 7000 DL could be used as evaluation criteria select the module and channel from the dropdown list to specify which channel value will be used AO channel The AO...

Страница 216: ...om the dropdown list first It provide as Basic Values Statistical Values and Others Information for selection And then select module and channel from the dropdown list to specify which power meter and...

Страница 217: ...ure Bluemix parameter must be a number otherwise 0 will be assigned PUE The PUE value could be used as evaluation criteria select the PUE from the dropdown list to specify which PUE value will be used...

Страница 218: ...ion v Click OK button to confirm the settings and return to the Rule settings page 11 1 2 Modbus Module Click on Modbus Module 4 options will appear as the following Discrete Input Coil Output Input R...

Страница 219: ...are going to include its value in the IF condition statements ii Define the evaluation criteria of the status in IF statement to be OFF or ON iii Click OK button to confirm the settings and return to...

Страница 220: ...from Modbus TCP RTU Slave module can be included in the IF condition statements the editing page for Holding Register Condition Setting is shown as below Figure11 9 Holding Register condition setting...

Страница 221: ...e used and then continue the following steps taking option V as an example i Specify the power meter and loop phase from the dropdown list of the Module Address section that you are going to include i...

Страница 222: ...Setting is shown as below Figure11 11 Microsoft Azure Connection Status condition setting Follow the steps below i Specify the connection status to be Offline or Online If the connection status of Mic...

Страница 223: ...ck OK button to confirm the settings and return to the Rule settings page 11 1 5 IBM Bluemix Click on IBM Bluemix 2 options will appear as the following Connection Status and Subscribe Message 11 1 5...

Страница 224: ...ubscribe Topic Select an operator from or iii Specify the user defined evaluation value If the content of this Subscribe Topic match the evaluation criteria the result of this condition evaluation wil...

Страница 225: ...ings page 11 1 6 2 Subscribe Topic The content of the Subscribe Topic can be included in the IF condition statements the editing page is shown as below Figure11 16 Subscribe Topic condition setting Fo...

Страница 226: ...setting page Follow the steps below i Specify the module from the dropdown list of the Module section that you are going to include its Connection Status in the IF condition statements ii And then sp...

Страница 227: ...n be used as evaluation criteria for IF condition statement the editing page for Schedule Condition Setting is shown as follow Figure11 19 Schedule condition setting page Follow the steps below i Sele...

Страница 228: ...ick OK button to confirm the settings and return to the Rule settings page 11 1 11 FTP Upload Status The status of FTP Upload Status can be used as evaluation criteria for IF condition statement the e...

Страница 229: ...IF condition statement Please note there must be at least one edited rule on PMC PMD controller for setting up Rule Status in the IF Condition Setting page The editing page for Rule Status Condition...

Страница 230: ...n value If this Internal Register value match the evaluation criteria the result of this condition evaluation will be true iv PMC PMD provides 12 value options you can compare them with the Input Regi...

Страница 231: ...to 11 1 1 2 DI Counter section for more detailed information v Click OK button to confirm the settings and return to the Rule settings page 11 1 16 Ping The Ping Status can be used as evaluation crite...

Страница 232: ...Register will be automatically displayed on the dropdown list To include subjects other than modules mentioned above in the THEN ELSE Action statement they have to be pre defined in Advanced Setting...

Страница 233: ...XV Board M 7000 DL 3 options will appear as the following DI Counter DO and AO 11 2 1 1 DI Counter You can reset DI counter of the XV Board M 7000 modules in the THEN ELSE Action statement the editin...

Страница 234: ...s to PWM Pulse width modulation modules the DO channel Action will be Start PWM or Stop PWM iii Specify the Frequency to be One Time or Repeat iv Specify the value in the Waiting Time field it means a...

Страница 235: ...the new AO channel value as the original AO channel value minus the value in Value field iii Set up the value in the Value field PMC PMD provides the following 12 value options to be used in the Valu...

Страница 236: ...used Holding Register using value of Holding Register from Modbus RTU TCP Slave modules select the module and address from the dropdown list to specify which channel value will be used Power Meter usi...

Страница 237: ...m the dropdown list to specify which value will be used Please Note The content of received MQTT subscribe topic or Azure Bluemix parameter must be a number otherwise 0 will be assigned PUE using valu...

Страница 238: ...ess of the Coil Output from the dropdown list of the Module Address section ii Specify the output value of Coil Output from the dropdown list of the Status field The output value can be OFF or ON iii...

Страница 239: ...ster value minus the value in Value field iii Set up the value in the Value field PMC PMD provides 12 value options Please refer to 11 2 1 3 AO section for more detailed information for value settings...

Страница 240: ...he action be executed how long the system will delay to execute the next Action The unit will be second s v Click OK button to confirm the settings and return to the Rule settings page 11 2 4 Microsof...

Страница 241: ...low the steps below i Select a pre set Publish message from the dropdown list of the Message field The Publish message will be displayed for you to verify if this is the message you are going to send...

Страница 242: ...e and Reset Variable 11 2 5 1 Function Status User can execute an action to change the connection operation between IBM Bluemix and PMC PMD in the THEN ELSE Action statement the editing page is shown...

Страница 243: ...Reset Variable You can reset the saved content of the subscribe variable from IBM Bluemix when executing a THEN ELSE Action statement the editing page is shown as below Figure11 38 IBM Bluemix Reset...

Страница 244: ...teps below i Select the specific Broker from the dropdown list of the Broker field ii Specify the Broker Function status to be Disable or Enable from the dropdown list of the Status field When the Act...

Страница 245: ...a THEN ELSE Action statement the editing page is shown as below Figure11 41 MQTT Reset Topic action setting page Follow the steps below i Select a pre set MQTT Subscribe Topic from the dropdown list...

Страница 246: ...nning the Timer will restart again The Reset action will reset the Timer and stop running the Timer iii Click OK button to save the settings The popup window will be closed and return to the Rule sett...

Страница 247: ...i In the SMS Alarm field specify the SMS Alarm you want to execute in Action from the dropdown list Please note the SMS Alarm you select has to be enabled in Advanced Setting The selected SMS Alarm me...

Страница 248: ...ion Setting section for the description of One Time and Repeat operation iii Input the value in the Waiting Time field it means after the action be executed how long the system will delay to execute t...

Страница 249: ...n the Message field specify the message you want to send in Action from the dropdown list The content of the selected Bot Service message will be displayed for you to verify if this is the message you...

Страница 250: ...11 2 15 Data Logger You can execute One Time Log in the Action statements to perform data recording one time only when an event is triggered User can also perform Start or Stop operation on data logge...

Страница 251: ...onfirm the settings and return to the Rule settings page 11 2 17 Internal Register You can modify the value of Internal Register in the THEN ELSE Action statement the editing page for Internal Registe...

Страница 252: ...iginal Internal Register value times the value in Value field Indicate assign the new Internal Register value as the original Internal Register value divided by the value in Value field iii Set up the...

Страница 253: ...ing code example demonstrates how to join the two registers into one floating point value For the compilers are different big endian or little endian the floating point composing order might be differ...

Страница 254: ...D 420x COM1 COM2 Modbus Address Coil Output 0x Discrete Input 1x Input Register 3x Holding Register 4x 0 59 PMC PMD System Data 1 60 75 RS 485 1 connection status 2 RS 485 1 Information 3 Internal Reg...

Страница 255: ...9 Power Meter Information Index 1 of RS 485 1 7 20250 20299 Power Meter Information Index 2 of RS 485 1 7 20300 20349 Power Meter Information Index 3 of RS 485 1 7 20350 20399 Power Meter Information...

Страница 256: ...40200 40249 Power Meter Information Index 1 of RS 485 2 7 40250 40299 Power Meter Information Index 2 of RS 485 2 7 40300 40349 Power Meter Information Index 3 of RS 485 2 7 40350 40399 Power Meter In...

Страница 257: ...6 of LAN 7 60200 60249 Power Meter Information Index 1 of LAN 7 60250 60299 Power Meter Information Index 2 of LAN 7 60300 60349 Power Meter Information Index 3 of LAN 7 60350 60399 Power Meter Inform...

Страница 258: ...0 1 UInt16 0 65535 Serial Number 8 300011 1 UInt16 0 65535 Boot Date Year 300012 1 UInt16 1752 Boot Date Month 300013 1 UInt16 1 12 Boot Date Day 300014 1 UInt16 1 31 Boot Time Hour 300015 1 UInt16 0...

Страница 259: ...s of M 7000 DL IR power meter and Modbus TCP RTU modules that are connected to the PMC PMD detailed information is shown as below Parameter Name Modbus Address Length Data Type Range 1x Discrete Input...

Страница 260: ...e connected to RS 485 2 300076 300091 1 UInt16 7002 7088 2133 4324 Module Address 1 64 The module type or NetID of power meter or Modbus TCP modules that are connected to LAN 300092 300107 1 UInt16 21...

Страница 261: ...ress the following section shows corresponding address information for different modules XV107 XV107A Parameter Name Modbus Address Length Data Type Range Coil Output 0x Unit Coil 8 Bits DO Ch 0 00020...

Страница 262: ...F 1 ON DI Ch 3 100203 1 Byte 0 OFF 1 ON DI Ch 4 100204 1 Byte 0 OFF 1 ON DI Ch 5 100205 1 Byte 0 OFF 1 ON DI Ch 6 100206 1 Byte 0 OFF 1 ON DI Ch 7 100207 1 Byte 0 OFF 1 ON DI Ch 8 100208 1 Byte 0 OFF...

Страница 263: ...t 0x Unit Coil 8 Bits DO Ch 0 000200 1 Byte 0 OFF 1 ON DO Ch 1 000201 1 Byte 0 OFF 1 ON DO Ch 2 000202 1 Byte 0 OFF 1 ON DO Ch 3 000203 1 Byte 0 OFF 1 ON DO Ch 4 000204 1 Byte 0 OFF 1 ON DO Ch 5 00020...

Страница 264: ...DI Counter 3 300206 2 UInt32 0 4294967295 DI Counter 4 300208 2 UInt32 0 4294967295 XV306 Parameter Name Modbus Address Length Data Type Range Coil Output 0x Unit Coil 8 Bits DO Ch 0 000200 1 Byte 0...

Страница 265: ...0203 1 Byte 0 OFF 1 ON Input Register 3x Unit Register 16 Bits DI Counter 0 300200 2 UInt32 0 4294967295 DI Counter 1 300202 2 UInt32 0 4294967295 DI Counter 2 300204 2 UInt32 0 4294967295 DI Counter...

Страница 266: ...Float Floating Point AI Ch 5 300210 2 Float Floating Point AI Ch 6 300212 2 Float Floating Point AI Ch 7 300214 2 Float Floating Point DI Counter 0 300216 2 UInt32 0 4294967295 DI Counter 1 300218 2 U...

Страница 267: ...ounter 3 300214 2 UInt32 0 4294967295 Holding Register 4x Unit Register 16 Bits AO Ch 0 400200 2 Float Floating Point AO Ch 1 400202 2 Float Floating Point 6 PUE Data This block stores information of...

Страница 268: ...e connection port and the index number PM_SA The starting Modbus address of Power Meter Information 2 of the connection port Power Meter Index number 1 x 50 4 Check the Modbus Address Table of each ty...

Страница 269: ...Byte 0 OFF 1 ON 3x Input Register Unit Register 16 Bits AI Ch 0 SA 300000 2 Float Floating Point AI Ch 1 SA 300002 2 Float Floating Point AI Ch 2 SA 300004 2 Float Floating Point AI Ch 3 SA 300006 2 F...

Страница 270: ...gth Data Type Range 0x Coils Output Unit Coil 8 Bits DO Ch 0 SA 000000 1 Byte 0 OFF 1 ON DO Ch 1 SA 000001 1 Byte 0 OFF 1 ON 1x Discrete Input Unit Coil 8 Bits DI Ch 0 SA 100000 1 Byte 0 OFF 1 ON 3x I...

Страница 271: ...nt AI Ch 1 SA 300002 2 Float Floating Point DI Counter 0 SA 300004 1 UInt16 0 65535 4x Holding Register Unit Register 16 Bits AO Ch 0 SA 400000 2 Float Floating Point M 7017 M 7017R M 7017C M 7017RC M...

Страница 272: ...M 7017Z 20 Single Ended AI channel Parameter Name Modbus Address Length Data Type Range 3x Input Register Unit Register 16 Bits AI Ch 0 SA 300000 2 Float Floating Point AI Ch 1 SA 300002 2 Float Floa...

Страница 273: ...SA 300008 2 Float Floating Point AI Ch 5 SA 300010 2 Float Floating Point AI Ch 6 SA 300012 2 Float Floating Point AI Ch 7 SA 300014 2 Float Floating Point AI Ch 8 SA 300016 2 Float Floating Point AI...

Страница 274: ...Register Unit Register 16 Bits AO Ch 0 SA 400000 2 Float Floating Point AO Ch 1 SA 400002 2 Float Floating Point AO Ch 2 SA 400004 2 Float Floating Point AO Ch 3 SA 400006 2 Float Floating Point M 700...

Страница 275: ...OFF 1 ON DI Ch 8 SA 100008 1 Byte 0 OFF 1 ON DI Ch 9 SA 100009 1 Byte 0 OFF 1 ON DI Ch 10 SA 100010 1 Byte 0 OFF 1 ON DI Ch 11 SA 100011 1 Byte 0 OFF 1 ON DI Ch 12 SA 100012 1 Byte 0 OFF 1 ON DI Ch 13...

Страница 276: ...SA 300002 2 UInt32 0 4294967295 M 7084 8 Counter Frequency Parameter Name Modbus Address Length Data Type Range 3x Input Register Unit Register 16 Bits DI Counter 0 SA 300000 2 UInt32 0 4294967295 DI...

Страница 277: ...5 1 Byte 0 OFF 1 ON DI Ch 6 SA 100006 1 Byte 0 OFF 1 ON DI Ch 7 SA 100007 1 Byte 0 OFF 1 ON 3x Input Register Unit Register 16 Bits DI Counter 0 SA 300000 2 UInt32 0 4294967295 DI Counter 1 SA 300002...

Страница 278: ...Point Temperature F SA 300006 2 Float Floating Point Dew Point C SA 300008 2 Float Floating Point Dew Point F SA 300010 2 Float Floating Point IR 210 Parameter Name Modbus Address Length Data Type Ran...

Страница 279: ...2 Float Floating Point kvar SA 300024 2 Float Floating Point kVA SA 300026 2 Float Floating Point PF SA 300028 2 Float Floating Point kWh SA 300030 2 Float Floating Point kvarh SA 300032 2 Float Floa...

Страница 280: ...Monthly SA 300080 2 Float Floating Point Daily Accumulated Electricity SA 300082 2 Float Floating Point Monthly Accumulated Electricity SA 300084 2 Float Floating Point Yearly Accumulated Electricity...

Страница 281: ...y Accumulated Electricity SA 300114 2 Float Floating Point Monthly Accumulated Electricity SA 300116 2 Float Floating Point Yearly Accumulated Electricity SA 300118 2 Float Floating Point Total Averag...

Страница 282: ...Float 1 65535 PM 2134 Parameter Name Modbus Address Length Data Type Range 3x Input Register Unit Register 16 Bits CT1 V SA 300000 2 Float Floating Point I SA 300002 2 Float Floating Point kW SA 3000...

Страница 283: ...Floating Point kW SA 300058 2 Float Floating Point kvar SA 300060 2 Float Floating Point kVA SA 300062 2 Float Floating Point PF SA 300064 2 Float Floating Point kWh SA 300066 2 Float Floating Point k...

Страница 284: ...Float Floating Point Monthly Accumulated Electricity SA 300100 2 Float Floating Point Yearly Accumulated Electricity SA 300102 2 Float Floating Point CT3 15 30 60 mins Actual Demand SA 300104 2 Float...

Страница 285: ...ectricity SA 300130 2 Float Floating Point Monthly Accumulated Electricity SA 300132 2 Float Floating Point Yearly Accumulated Electricity SA 300134 2 Float Floating Point 3x Input Register Unit Regis...

Страница 286: ...oating Point kvar SA 300006 2 Float Floating Point kVA SA 300008 2 Float Floating Point PF SA 300010 2 Float Floating Point kWh SA 300012 2 Float Floating Point kvarh SA 300014 2 Float Floating Point...

Страница 287: ...Point kVAh SA 300070 2 Float Floating Point Phase A 15 30 60 mins Actual Demand SA 300072 2 Float Floating Point 15 30 60 mins Forecast Demand SA 300074 2 Float Floating Point Max Demand Hourly SA 300...

Страница 288: ...s Forecast Demand SA 300106 2 Float Floating Point Max Demand Hourly SA 300108 2 Float Floating Point Max Demand Daily SA 300110 2 Float Floating Point Max Demand Monthly SA 300112 2 Float Floating Po...

Страница 289: ...loat Floating Point Frequency Phase C SA 300144 2 Float Floating Point Frequency Maximum SA 300146 2 Float Floating Point 3x Input Register Unit Register 16 Bits Power Meter Type PM_SA 300000 1 Int16...

Страница 290: ...kvarh SA 300014 2 Float Floating Point kVAh SA 300016 2 Float Floating Point CT2 V SA 300018 2 Float Floating Point I SA 300020 2 Float Floating Point kW SA 300022 2 Float Floating Point kvar SA 3000...

Страница 291: ...SA 300048 2 Float Floating Point Yearly Accumulated Electricity SA 300050 2 Float Floating Point CT2 15 30 60 mins Actual Demand SA 300052 2 Float Floating Point 15 30 60 mins Forecast Demand SA 3000...

Страница 292: ...ister Unit Register 16 Bits CT1 V SA 300000 2 Float Floating Point I SA 300002 2 Float Floating Point kW SA 300004 2 Float Floating Point kvar SA 300006 2 Float Floating Point kVA SA 300008 2 Float Fl...

Страница 293: ...2 Float Floating Point PF SA 300064 2 Float Floating Point kWh SA 300066 2 Float Floating Point kvarh SA 300068 2 Float Floating Point kVAh SA 300070 2 Float Floating Point CT1 15 30 60 mins Actual De...

Страница 294: ...city SA 300102 2 Float Floating Point CT3 15 30 60 mins Actual Demand SA 300104 2 Float Floating Point 15 30 60 mins Forecast Demand SA 300106 2 Float Floating Point Max Demand Hourly SA 300108 2 Floa...

Страница 295: ...CT2 SA 300138 2 Float Floating Point Frequency CT3 SA 300140 2 Float Floating Point Frequency CT4 SA 300142 2 Float Floating Point 3x Input Register Unit Register 16 Bits Power Meter Type PM_SA 300000...

Страница 296: ...e 1 Phase A CT1 2 Phase B CT2 3 Phase C CT3 Harmonic Selector Submeter 2 SA 400001 1 UInt16 0 Disable 1 Phase A CT4 2 Phase B CT5 3 Phase C CT6 Harmonic Selector Submeter 3 SA 400002 1 UInt16 0 Disabl...

Страница 297: ...Point kvarh SA 300014 2 Float Floating Point kVAh SA 300016 2 Float Floating Point Phase B CT2 V SA 300018 2 Float Floating Point I SA 300020 2 Float Floating Point kW SA 300022 2 Float Floating Poin...

Страница 298: ...oat Floating Point kWh SA 300084 2 Float Floating Point kvarh SA 300086 2 Float Floating Point kVAh SA 300088 2 Float Floating Point Phase B CT5 V SA 300090 2 Float Floating Point I SA 300092 2 Float...

Страница 299: ...oat Floating Point kWh SA 300156 2 Float Floating Point kvarh SA 300158 2 Float Floating Point kVAh SA 300160 2 Float Floating Point Phase B CT8 V SA 300162 2 Float Floating Point I SA 300164 2 Float...

Страница 300: ...oat Floating Point kWh SA 300228 2 Float Floating Point kvarh SA 300230 2 Float Floating Point kVAh SA 300232 2 Float Floating Point Phase B CT11 V SA 300234 2 Float Floating Point I SA 300236 2 Float...

Страница 301: ...oat Floating Point kWh SA 300300 2 Float Floating Point kvarh SA 300302 2 Float Floating Point kVAh SA 300304 2 Float Floating Point Phase B CT14 V SA 300306 2 Float Floating Point I SA 300308 2 Float...

Страница 302: ...oat Floating Point kWh SA 300372 2 Float Floating Point kvarh SA 300374 2 Float Floating Point kVAh SA 300376 2 Float Floating Point Phase B CT17 V SA 300378 2 Float Floating Point I SA 300380 2 Float...

Страница 303: ...oat Floating Point kWh SA 300444 2 Float Floating Point kvarh SA 300446 2 Float Floating Point kVAh SA 300448 2 Float Floating Point Phase B CT20 V SA 300450 2 Float Floating Point I SA 300452 2 Float...

Страница 304: ...oat Floating Point kWh SA 300516 2 Float Floating Point kvarh SA 300518 2 Float Floating Point kVAh SA 300520 2 Float Floating Point Phase B CT23 V SA 300522 2 Float Floating Point I SA 300524 2 Float...

Страница 305: ...30 60 mins Forecast Demand SA 300578 2 Float Floating Point Max Demand Hourly SA 300580 2 Float Floating Point Max Demand Daily SA 300582 2 Float Floating Point Max Demand Monthly SA 300584 2 Float Fl...

Страница 306: ...A 300612 2 Float Floating Point Max Demand Daily SA 300614 2 Float Floating Point Max Demand Monthly SA 300616 2 Float Floating Point Daily Accumulated Electricity SA 300618 2 Float Floating Point Mon...

Страница 307: ...urly SA 300644 2 Float Floating Point Max Demand Daily SA 300646 2 Float Floating Point Max Demand Monthly SA 300648 2 Float Floating Point Daily Accumulated Electricity SA 300650 2 Float Floating Poi...

Страница 308: ...0676 2 Float Floating Point Max Demand Daily SA 300678 2 Float Floating Point Max Demand Monthly SA 300680 2 Float Floating Point Daily Accumulated Electricity SA 300682 2 Float Floating Point Monthly...

Страница 309: ...SA 300708 2 Float Floating Point Max Demand Daily SA 300710 2 Float Floating Point Max Demand Monthly SA 300712 2 Float Floating Point Daily Accumulated Electricity SA 300714 2 Float Floating Point M...

Страница 310: ...A 300740 2 Float Floating Point Max Demand Daily SA 300742 2 Float Floating Point Max Demand Monthly SA 300744 2 Float Floating Point Daily Accumulated Electricity SA 300746 2 Float Floating Point Mon...

Страница 311: ...urly SA 300772 2 Float Floating Point Max Demand Daily SA 300774 2 Float Floating Point Max Demand Monthly SA 300776 2 Float Floating Point Daily Accumulated Electricity SA 300778 2 Float Floating Poi...

Страница 312: ...A 300804 2 Float Floating Point Max Demand Daily SA 300806 2 Float Floating Point Max Demand Monthly SA 300808 2 Float Floating Point Daily Accumulated Electricity SA 300810 2 Float Floating Point Mon...

Страница 313: ...urly SA 300836 2 Float Floating Point Max Demand Daily SA 300838 2 Float Floating Point Max Demand Monthly SA 300840 2 Float Floating Point Daily Accumulated Electricity SA 300842 2 Float Floating Poi...

Страница 314: ...A 300868 2 Float Floating Point Max Demand Daily SA 300870 2 Float Floating Point Max Demand Monthly SA 300872 2 Float Floating Point Daily Accumulated Electricity SA 300874 2 Float Floating Point Mon...

Страница 315: ...urly SA 300900 2 Float Floating Point Max Demand Daily SA 300902 2 Float Floating Point Max Demand Monthly SA 300904 2 Float Floating Point Daily Accumulated Electricity SA 300906 2 Float Floating Poi...

Страница 316: ...A 300932 2 Float Floating Point Max Demand Daily SA 300934 2 Float Floating Point Max Demand Monthly SA 300936 2 Float Floating Point Daily Accumulated Electricity SA 300938 2 Float Floating Point Mon...

Страница 317: ...urly SA 300964 2 Float Floating Point Max Demand Daily SA 300966 2 Float Floating Point Max Demand Monthly SA 300968 2 Float Floating Point Daily Accumulated Electricity SA 300970 2 Float Floating Poi...

Страница 318: ...A 300996 2 Float Floating Point Max Demand Daily SA 300998 2 Float Floating Point Max Demand Monthly SA 301000 2 Float Floating Point Daily Accumulated Electricity SA 301002 2 Float Floating Point Mon...

Страница 319: ...urly SA 301028 2 Float Floating Point Max Demand Daily SA 301030 2 Float Floating Point Max Demand Monthly SA 301032 2 Float Floating Point Daily Accumulated Electricity SA 301034 2 Float Floating Poi...

Страница 320: ...A 301060 2 Float Floating Point Max Demand Daily SA 301062 2 Float Floating Point Max Demand Monthly SA 301064 2 Float Floating Point Daily Accumulated Electricity SA 301066 2 Float Floating Point Mon...

Страница 321: ...int Submeter 2 VTHD SA 301092 2 Float Floating Point Submeter 2 ITHD SA 301094 2 Float Floating Point Submeter 3 VTHD SA 301096 2 Float Floating Point Submeter 3 ITHD SA 301098 2 Float Floating Point...

Страница 322: ...Floating Point Frequency CT6 Phase C SA 301132 2 Float Floating Point Frequency Maximum SA 301134 2 Float Floating Point Frequency CT7 Phase A SA 301136 2 Float Floating Point Frequency CT8 Phase B SA...

Страница 323: ...nt Frequency Maximum SA 301174 2 Float Floating Point Frequency CT22 Phase A SA 301176 2 Float Floating Point Frequency CT23 Phase B SA 301178 2 Float Floating Point Frequency CT24 Phase C SA 301180 2...

Страница 324: ...Ratio 2 PM_SA 300014 2 Float 0 01 655 35 CT Ratio 1 PM_SA 300016 2 Float 1 65535 CT Ratio 2 PM_SA 300018 2 Float 1 65535 CT Ratio 3 PM_SA 300020 2 Float 1 65535 CT Ratio 4 PM_SA 300022 2 Float 1 6553...

Страница 325: ...Data Number Coil Output 11 7 Discrete Input 0 10 Input Register 7 4 32 bit Floating Point Holding Register 20 3 32 bit Floating Point The allocation of the Modbus Address in PMC PMD for the Coil Outpu...

Страница 326: ...13407 9 10008 13408 10 10009 13409 The allocation of the Modbus Address in PMC PMD for the Input Register setting of this Modbus RTU module is shown as below Input Register Index The Modbus Address in...

Страница 327: ...h to the specific position to delete the data logger files and reset the accumulated values of the power meter which connect to PMC PMD The following figure shows the location of the Rotary Switch of...

Страница 328: ...ail account of the Administrator 1 Switch the Rotary Switch to position 8 2 Connect to PMC PMD Login webpage via Web browser Now a Forget password message will be displayed under the password field Cl...

Страница 329: ...d values of the power meter 1 Switch the Rotary Switch to position 8 2 Connect to PMC PMD login webpage via Web browser and login as the Administrator 3 After login into the system the message box of...

Страница 330: ...up the GTM 203M 3GWA with PMD Hardware installation 1 Install the SIM card and antenna on the GTM 203M 3GWA and connect the device with Power 10VDC 30VDC 2 Connect the GTM 203M 3GWA and PMD by USB cab...

Страница 331: ...ct the M 7000 DL modules to the PC with DCON Utility installed via RS 485 cable make sure the RS 485 cable is properly connected For PC to receive RS 485 signals a RS 232 to RS 485 or a USB to RS 485...

Страница 332: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 317 B Start the DCON Utility and verify if the COM Port parameters are accurate...

Страница 333: ...ted to the PC C Click on the M 7000 module to bring up the Configuration Window and setup the parameters such as Address Baudrate for the module The Configuration Window will be shown as follow using...

Страница 334: ...as below http ftp icpdas com pub cd 8000cd napdos driver dcon_utility manual 3 For others ICP DAS I O module please refer to related user manual for the configuration setting In order to accurately co...

Страница 335: ...Index ifDescr IfType ifMtu ifSpeed ifPhysAddress ifAdminStatus ifOperStatus ifLastChange ifInOctets ifInUcastPkts ifInNUcastPkts ifInDiscards ifInErrors ifInUnknownProtos ifOutOctets ifOutUcastPkts if...

Страница 336: ...tcpAttempFails tcpEstabResets tcpCurrEstab tcpInSegs tcpOutSegs tcpRetransSegs tcpConnState tcpConnLocalAddress tcpConnLocalPort tcpConnRemAddress tcpConnRemPort tcpInErrs tcpOutRsts UDP UdpInDatagra...

Страница 337: ...missionsFactor cellularIP cellularSignal cellularSignalPercent Power Meter1 On Com3 com3pm1Index com3pm1Interface com3pm1ModbusID com3pm1Name com3pm1PTIndex com3pm1PTValue com3pm1PTIndex com3pm1CTValu...

Страница 338: ...ed information above but with prefix com4pm16 instead The SNMP Variables naming rule of the power meters on LAN The Power Meter1 SNMP Variables are similar as listed information above but with prefix...

Страница 339: ...rule of the I O modules on Com3 The I O Module1 SNMP Variables are shown as above with prefix com3io1 the I O Module2 SNMP Variables are similar to listed information above but with prefix com3io2 in...

Страница 340: ...hMaxDemandM com1pm1ChElectricityD com1pm1ChElectricityM com1pm1ChElectricityY com1pm1DOIndex com1pm1DOName com1pm1DOValue com1pm1HarmonicSubmeterIndex com1pm1HarmonicSelector com1pm1HarmonicVTHD com1p...

Страница 341: ...ndex com1io1CoilOutputName com1io1CoilOutputValue com1io1CoilOutputModbusAdd com1io1CoilOutputAdvFunction com1io1InputRegIndex com1io1InputRegName com1io1InputRegValue com1io1InputRegModbusAdd com1io1...

Страница 342: ...isted information above but with prefix com2io16 instead The SNMP Variables naming rule of the I O modules on LAN The I O Module1 SNMP Variables are similar as listed information above but with prefix...

Страница 343: ...n skip it in the setting The Command consist a set of parameters Each parameter consist one name and one value The name and the value of a parameter are linked by symbol The parameters are linked by s...

Страница 344: ...ed value will be shown in the JSON format In the above example the value of Internal Register 1 is 2 3 It is located in value section of the result area JSONP Supported If user wants to enable the JSO...

Страница 345: ...ace is XV Board or Ethernet skip this parameter If the I O interface is COM Port it is the COM Port number Value 0 COM0 1 COM1 so on Name module_no Description The index number of the module If the I...

Страница 346: ...ary Name ch_value Description The value you want to assign to the output channel Value Digital type channel 0 or 1 Analog type channel Number Infrared module command index Response The channel is exis...

Страница 347: ...t it is for the COM Port number Value 0 COM0 1 COM1 so on Name module_no Description The index number of the module Value Integer start from 1 Name ch_type Description The channel type Value Modbus Mo...

Страница 348: ...tion ITHD frequency Frequency Name ch_addr Description The channel address Value The ch_addr is Modbus Data Address for the Modbus module For other module the ch_addr is the channel sequence number st...

Страница 349: ...EXIST Password error status PASSWORD_INCORRECT Get all channel value of the remote I O module or Power module Command job get_module_val if_type val com_port val module_no val Parameters Name if_type...

Страница 350: ...ger start from 1 Response The module is existed If it is a Modbus module status OK result ci address 32 value 0 co if there is no channel of this type ri address 10 value 1 3 ro address 22 value 2 5 c...

Страница 351: ...4 2000 93 kvarh 22803 2 24 7 kvah 51267 4 3211 1 kw_now 2 873 0 kw_predict 2 873 0 maxkw_hour 2 881 0 maxkw_day 2 892 0 maxkw_month 3 076172 0 kwh_day 3 712 0 kwh_month 432 0645 0 kwh_year 898 1973 0...

Страница 352: ...d status network no 3 connection OFFLINE Password error status PASSWORD_INCORRECT Set up the value of a specific Internal Register Command job set_ir_val ir_no val ir_value val Parameters Name ir_no D...

Страница 353: ...status PASSWORD_INCORRECT Get the value of a specific Internal Register Command job get_ir_val ir_no val Parameters Name ir_no Description The index number of the Internal Register Value Integer star...

Страница 354: ...ed Command job get_irs_val Parameters None Response Normal Status status OK result no 1 value 100 Password error status PASSWORD_INCORRECT Get the system time Command job get_system_time Parameters No...

Страница 355: ...the current free space of the micro SD card Command job get_sdcard_space Parameters None Response Normal Status status OK result free_space 1560 Free space Unit is MB No microSD card detected status S...

Страница 356: ...ceive the specific topics to complete the action Following will list the format of Public topic to the related output channel of module and Internal Register DO channel of ICP DAS XV Board Topic Prefi...

Страница 357: ...e module_no coil_output channel_ address Prefix Please refer to 9 3 MQTT Setting interface com3 com4 or lan module_no 1 16 channel_address 0 99999 Message 0 or 1 The Holding Register channel of others...

Страница 358: ...indicates the message published by PMC PMD to inform IoT Cloud platform the update of the power data or I O channel data CHANNEL_OUTPUT If PMC PMD receives the message in the type of CHANNEL_OUTPUT t...

Страница 359: ...kw kW kvar kvar kva kVA pf PF kwh kWh kvarh kvarh kvah kVAh kw_now Actual Demand kw_predict Forecast Demand maxkw_hour Max Demand Hourly maxkw_day Max Demand Daily maxkw_month Max Demand Monthly mwh_d...

Страница 360: ...following is the format to publish a message with the kwh value of Loop 2 which resides at the PM 3114 power meter with module number 5 to IoT Cloud platform The power module is connected to the COM3...

Страница 361: ...a format of the received message from IoT Cloud platform it is used to change the value of AO channel 1 of XV Board of PMC 5231 to 3 6 The following is a format of the received message from IoT Cloud...

Страница 362: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 347 msg_type CHANNEL_OUTPUT if_type 1 com_port 4 module_no 3 ch_type ao ch_addr 2 nickname fan speed value 5 0...

Страница 363: ...module is powered on RUN Red ON The module is functioning normally 3G 4G OFF and one flash per 2 seconds The modem is not functioning or no SIM card inside ON and one flash per 2 seconds The modem is...

Страница 364: ...mand IoTstar can be quickly integrated with the Cloud platforms data analysis tools Power BI Google Data Studio or SCADA system etc to help users quickly build the IoT Big Data Cloud application WISE...

Страница 365: ...PMC PMD page to open the parameter setting page of IoTstar Connection Setting then click the button next to ICP DAS IoTstar Trial Service ii On the account application page of IoTstar Trial enter the...

Страница 366: ...n process of the trial account iv When the trial account is successfully activated the page will display the Successfully activated message as below v When the trial account is successfully activated...

Страница 367: ...s to PMC PMD After that the PMC PMD controller will connect to the IoTstar Trial account you applied vii Go to https iotstartrial icpdas com to visit the login page of the IoTstar Trial enter the Acco...

Страница 368: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 353 For more information about IoTstar IoT cloud management software please refer to IoTstar official website...

Отзывы: