ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
6
2
Before Installation
Modify PMC/PMD‘s network settings to fit current network environment settings,
and the default network settings of PMC/PMD is as follow:
IP
:
192.168.255.1
Subnet mask
:
255.255.0.0
Gateway address
:
192.168.0.1
DNS Server address
:
8.8.8.8 (default: Google DNS Server)
Steps
(1)
Modify the network settings of the PC or Notebook to be the same network
segment as PMC/PMD. For example:
IP
:
192.168.255.10
Subnet mask
:
255.255.0.0
Gateway address
:
192.168.0.1
(2)
Connect PMC/PMD
LAN1
to PC by network cable. (PMC/PMD is capable
of auto-crossover)
(3)
Start the browser and input
(4)
Input default administrator password “
Admin
” to login into the page.
(5)
After login in PMC/PMD web page, go to System Setting Network Setting,
modify the network setting to fit current network environment. More detailed
setting information please refer to
(6)
Save the settings and connect PMC/PMD to the network.
Please Note:
1.
Before installing PMC/PMD, please finish the hardware installation of the
ICP DAS Power meter modules, and make sure all wiring connections are
accurate.
2.
If there are the M-7000/DL/IR modules or Modbus TCP/RTU Slave modules
which will connect with PMC/PMD, please also finish the hardware
installation of the M-7000/DL/IR modules or Modbus TCP/RTU Slave
modules, and make sure all wiring connections are accurate.
3.
One PMC/PMD allows connections to at most 24 ICP DAS Modbus power
meters (including Modbus RTU and Modbus TCP power meters.).
4.
One PMC/PMD allows connections to at most 8 Modbus TCP/RTU Slave
I/O modules.
5.
A single I/O interface allows connections to at most 16 devices (Power
meters and I/O modules).