![ICP DAS USA PMD series Скачать руководство пользователя страница 135](http://html1.mh-extra.com/html/icp-das-usa/pmd-series/pmd-series_user-manual_3622279135.webp)
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
120
If users select “32-bit Signed Long”, “32-bit Unsigned Long”,
or “32-bit Floating Point”, the option “Inverse(Big Endian)”
will appear. Enable “Inverse(Big Endian)” to receive the data in
big endian format correctly.
After finishing the “Start Address”, “Data Number”, and “Type”
setting, click on “Add” button. A new Input Register address
block will be added to the Modbus address mapping table
(shown as below). All added address blocks will be located in
sequences staring from the Starting Address (The address
number on the first column of the “Local Address” indicates the
local Modbus address of PMC/PMD to keep the Input Register
data.).
Figure 7-48 shows an example about Input Register setting for a
Modbus RTU module. The starting Modbus address of the Input
Register block is 30010(30000 + 10), it requires to set 3
continuous Input Register data in the setting, and the data type
is “32-bit Floating Point”. So that these retrieved Input Register
data will be kept in PMC/PMD Address 30300, 30302, and
30304.
Figure7-48 :
Input Register Setting Example for Modbus RTU Module
To modify the starting address or quantity setting, please click