ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
124
Figure7-50 :
Input Register Setting Example for Modbus RTU Module
To modify the starting address or quantity setting, please click
on the setting block to perform the modification. The user could
also modify Type, Scale Ratio, Offset and Deadband on this
interface. For more detailed information, please refer to above
section “The Input Register Setting of Modbus RTU Module”.
If the user wants to assign a Nickname for the address blocks,
the user can click on the “Nickname Setting” tab, and then input
the Nickname for each address block. The Nickname will be
shown in the “I/O Information” and “Rule Setting” pages.
After all Holding Register settings of the Modbus RTU module
are completed, click “OK” button to save the changes.
7.3.7
Modbus TCP Module Setting
PMC/PMD allows connections to modules that support Modbus TCP
Slave protocol for offering I/O interface function. Through Modbus