I-7530, I-7530A, I-7565, I-7530-FT, tM-7530, tM-7530A, tM-7565 User Manual Version 1.6
Page:
50
Copyright © 2018 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]
3.5 Saving and default value
After the user selects the parameters in the "setting screen", and click the "Save All
Setting" button to write the parameters into the EEPROM of the CAN converter, but if
the user wants to restore the parameters to the factory default values, please click the
"Load Default Setting" button to restore all the parameters of the "Setting Screen" to the
default values, and then click the "Save All Settings" button to write the parameters into
the EEPROM of the CAN converter. Finally, set the Init/Normal of DIP switch to Normal,
and power on the CAN converter again to start using these parameters.
The default values of CAN converter as below table:
UART side
Baud Rate
115200
:
I-7530
、
I-7530A
、
tM-7530
、
tM-
7530A
、
tM-7565 and I-7530-FT
921600
:
I-7565
Data Bit
8
Stop Bit
1
Parity Bit
None
Add Checksum
Disable
Error Response
Disable
Timestamp Response
Disable
CAN side
CAN specification
2.0A
CAN baud rate
125k
acceptance code (ACC)
000
acceptance mask (ACM)
000
Communacation mode
mode
Normal mode