I-7530, I-7530A, I-7565, I-7530-FT, tM-7530, tM-7530A, tM-7565 User Manual Version 1.6
Page:
68
Copyright © 2018 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]
4.11 P3SBCCCCCCCCMMMMMMMM [CHK]<CR>
Description:
Set the parameter configuration of the CAN side, but do not store it
Syntax: P3SBCCCCCCCCMMMMMMMM[CHK]<CR>
P3
Command character
S
CAN Specification 2.0A/2.0B
B
CAN Baud rate
CCCCCCCC
CAN ID filter acceptance code (ACC)
MMMMMMM
CAN ID filter acceptance mask (ACM)
Table: CAN baud rate
Code B
Description
0
CAN baud rate 10K
1
CAN baud rate 20K
2
CAN baud rate 50K
3
CAN baud rate 100K
4
CAN baud rate 125K
5
CAN baud rate 250K
, I-7530-FT not supported
6
CAN baud rate 500K
, I-7530-FT not supported
7
CAN baud rate 800K
, I-7530-FT not supported
8
CAN baud rate 1000K
, I-7530-FT not supported
9
CAN baud rate 83.3K
, I-7530-FT not supported
Response:
Valid command: No response, and the CAN bus configuration parameters will be
changed.
Invalid command: ?<Error Code><CR>
Note
:
In order to communicate with the computer to receive error information, the user must
enable the "Error Response" function in the CAN converter software. For the CAN ID filter
setting, please refer to "Set CAN ID Filter" in Section 3.3.