Features
• Thermostat Compatibility
• Limited Recycle:
– Number of recycle trials is limited to three per heat call
– Lockout results when flame extinguishes three times without a successful heat
call
• Pump Priming Cycle:
– Place the oil primary control in purge cycle by pressing and releasing the unit’s
reset button when in delayed valve-on, safety check, ignition, or carry-over periods.
– For this cycle only, lockout timing will extend to 4 minutes with ignition set in
intermittent mode
– To reset the unit for entry to pump priming cycle, press and hold the reset button
until the LED flashes (approximately 30 seconds)
– The oil primary control will revert to its labeled interrupted and safety switch
timing conditions.
– Pump priming cycle entrance can only occur if no lockouts have taken place since
the most recent successful call for heat
• Disable Function:
– Press and hold the reset button to disable all functions
– Re-enable by releasing the reset button
– Restart will occur at the start of the normal heat cycle on safety check
• Limited Reset (Restricted Mode):
– Limit unburned oil accumulation in the combustion area by resetting the control up
to three times