Application
ICM’s Interrupted Ignition Oil Primary Control is ideal for residential oil-fired burners
used in boilers, forced air furnaces, and water heaters.
The oil primary:
• Controls fuel oil
• Senses the flame
• Commands ignition spark
• Triggers a remote alarm circuit when in lockout
The ICM Interrupted Ignition Oil Primary Control can be used with hydronic and forced
air systems. Line voltage switching controllers typically control the start and stop of
the combustion sequences when the oil primary control is used with hydronic systems.
With forced air systems, low voltage mechanical and electronic thermostats control
the start and stop of the combustion process.
The ICM Interrupted Ignition Oil Primary Control operates a valve to prevent oil flow
when the burner motor runs prior to combustion (the valve-on delay) and when the
burner motor runs after combustion (the burner motor-off delay).
The ICM Interrupted Ignition Oil Primary Control is intended for use only on oil burning
appliances that do not require pre-purge and post-purge as a safety related function.
The purposes of the valve-on and burner motor-off delays in the ICM Interrupted
Ignition Oil Primary Control are to help establish draft and reduce the problems
associated with oil after-drip.