![ICM Controls ICM1511 Series Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/icm-controls/icm1511-series/icm1511-series_custom-options-manual-and-installation-instructions_610899013.webp)
Check Safety Features
Safe Start
1. Place a jumper across cad cell terminals.
2. Follow procedure to turn on burner. Burner must not start, indicator light turns on
and control remains in Idle Mode.
Simulate Flame Failure:
1. Follow procedure to turn on burner.
2. Close hand valve in oil supply line.
3. Device enters recycle mode.
4. Device tries to restart system after approximately 60 seconds.
5. Safety switch locks out approximately in safety switch timing indicated on label.
Indicator light flashes 1/2 second on, 1/2 second off. Ignition and motor stop and oil
valve closes.
Simulate Ignition Failure:
1. Follow starting procedure to turn on burner, but do not open oil supply hand valve.
2. Observe that safety switch locks out approximately within safety switch timing as
indicated on the label. Indicator light flashes 1/2 second on, 1/2 second off. Ignition
and motor stop and oil valve closes.