Troubleshooting Tips
Condition
Check for:
Burner does not
start with call for
heat.
Check that the limit switches are closed and contacts clean.
Check for 120 VAC line voltage; If indicator light is on, the Cad cell
controller may be defective, sees external light, or connections are
shorted.
Burner starts, then
locks out on safety.
Check that limit switches are closed and contacts clean.
Check for proper line voltage.
Check to see if Cad cell or controller is seeing external light.
Try resetting oil primary control.
Verify that control is not in restricted mode.
Check spark ignitor.