Thermostat calls
for heat
5. Control enters Ignition Carry-Over period (continues to spark for 10 to 30
seconds.
a. Turns on indicator light.
b. If flame is lost and lockout time has not expired, Oil Primary Control
returns to Trial for Ignition period.
c. If flame is lost and lockout time has expired, Oil Primary Control enters
Recycle Mode.
6. Carry-Over time expires; ignitor turns off.
7. Enters Run Mode:
a. Flame is monitored until call for heat ends or flame is lost. If flame is lost:
(1) Control enters Recycle Mode.
(2) Recycle time starts (60 seconds).
(3) Burner and valve are turned off.
(4) Indicator light flashes at 2 seconds on, 2 seconds off.
(5) Returns to Idle Mode at end of Recycle Mode.
Call for heat is
satisfied.
1. ICM1511*, ICM1514* (if burner motor-off delay is disabled):
a. Burner motor and oil valve shut off.
b. Indicator light turns off.
2. ICM1511*, ICM1512*, ICM1513* (if burner motor-off delay is enabled):
a. Oil valve shuts off.
b. Burner motor runs for selected burner motor-off delay time.
c. Burner motor turns off.
d. Device returns to Idle Mode.
Reset Button
pushed two times
without device
completing a call
for heat.
1. Oil Primary Control enters Restricted Mode.
2. Indicator light flashes and 1/2 second on, 1/2 second off.
3. Reset device by pressing and holding reset button for a minimum of 30
seconds.