User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 6
Indice : g
2. Protection and operation functions
2.1 Protection functions NPM800 and NPM800R - NPM800RE
♦
ANSI 49 Thermal overload function, with inhibition of closing on load.
♦
Short-circuit protection, with one ANSI 50 threshold
♦
Earth fault protection, with one ANSI 51N threshold
♦
Minimum load protection (pump unpriming) ANSI 37
♦
Inverse over-current protection with one ANSI 46 threshold for the detection of
unbalance, loss or inversion of phase ANSI 46
♦
Too long starts ANSI 48 and locked rotor Protection ANSI 51LR
♦
ANSI 66 number of starts authorisation Function
♦
Load-shedding and re acceleration Function by external input
♦
ANSI 50BF & 50NBF, circuit breaker failure function by checking of the
disappearance of the phase current. (Configuration available only by the setting
software)
♦
ANSI 86, latching output contacts (Configuration available only by the setting
software)
♦
ANSI 74TC, trip circuit supervision (Configuration only by the setting software)
2.2 Operation functions NPM800 and NPM800R - NPM800RE
♦
Two setting groups
♦
Assignment of digital inputs
♦
Assignment of relay outputs
♦
User programmable LEDs
♦
Monitoring of trips and reclosings
♦
Help in circuit breakers maintenance: number of operations with alarm threshold
♦
Storage of the last 250 events
♦
Storage of four 52 periods disturbance recordings, according to COMTRADE
standard
♦
4 or 8 User configurable generic functions.
2.3 Locally available User’s functions
Locally, the following functions are available:
♦
Choice of language
♦
Setting in or out of order of the functions
♦
Customized identification of protection
♦
Setting of adjustment and primary values for the two tables
♦
Assignment of the inputs / outputs
♦
Reading of fault values
♦
Reading of each memorized value: measurements and counters
♦
Reset of counters
♦
Reading of events
♦
Configuration of disturbance recording and local trigger
♦
Configuration of Modbus® communication.