User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 40
Indice : g
6. Content of an event
Events are different according to information recorded when fault occurs. There are three
different types of structures of event.
They can be read with the local MMI, the setting software (RS232 link) and the Modbus
communication network.
6.1 Events generated on 50/51N/37/46 thresholds (NPM800 and NPM800R -
NPM800RE)
Events are recorded as soon as a trip or alarm threshold of the current functions is reached:
♦
INST PH FAULT
♦
TRIP PH FAULT
♦
INST Io FAULT
♦
TRIP Io FAULT
♦
INST UNBALA PH
♦
TRIP UNBALA PH
♦
TRIP START LON
♦
TRIP STALL ROT
♦
TRIP LOSS LOAD
♦
TRIP DELOAD
Detail of available information can be consulted for each event, in accordance with the list
below:
MAIN MENU
EVENTS
List of the last 250 events
TRIP PH FAULT S
17/06 14:22:00 R
Type of fault Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/
Synchronous
17/16/13
14:22:00.990
Day: Month: Year
Hour: Minute: Second. Millisecond
SETTING
set 1
Active setting group when tripping
set 1 or set 2
CURRENT I1
745 A
Current of phase 1 measured during the event
CURRENT I3
743 A
Current of phase 3 measured during the event