User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 21
Indice : g
5.5 Generic functions menu
This menu allows the parameter setting of 4 or 8 (according option or relay type) customized
functions: setting in and out of order, adjustment of the time delays, assignment of the output
units and assignment of a digital input.
MAIN MENU
GENERIC FUNCTION
Parameters of the customized
functions
FCT GENERIC 1
Inactive
Choose Trip or Report to use
function 1.
Trip or Disable or Report*
TEMP GENERIC 1
0.06 s
Set the time delay of function 1
0.04 to 300.00s
RELAY GENERIC 1
A B C D
Select relay to assign to function 1
See chap 4 to choose a relay
or to modify the assignment
RELAY GENERIC 1
E F G
(relays D, E, F, G if option
available)
DIG.INP.GENER. 1
Input 1
Display of input selected for function
1
No input, Input 1 to 8 (or 1 to
4 according option)
NAME GENERIC 1
ALARM AERO
Display of label of function 1
No input, Input 1 to 8 (or 1 to
4 according option)
..................
..............
* The « Report » mode is available since V2.20 firmware.