User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 20
Indice : g
EARTH FLT DELAY
0.06 s
Set the value of the time delay of
earth fault function
0.04 to 3 s
EARTH FLT THRESH
0.1 * In
Set the value of the threshold of earth
fault function
0.03 to 0.4 * In
EARTH INST.RELAY
A B C D
Select relay to assign to the earth fault
instantaneous function
See chap 4 to choose a relay
or to modify the assignment
EARTH INST. RELAY
E F G
(relays D, E, F, G if option
available)
EARTH TRIP RELAY
A B C D
Select relay to assign to the earth fault
trip function
See chap 4 to choose a relay
or to modify the assignment
EARTH TRIP RELAY
E F G
(relays D, E, F, G if option
available)