User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 36
Indice : g
CLEAR REL. INPUT
E5
Display of input assigned to reset
of relays
No input, Input 1 to 8 (or 1 to 4
according option)
TRIP PULSE
100 ms
Setting of minimum duration of trip
pulse
100 to 500 ms
MAX A2 CUTOFF
200000 kA2
Adjustment of the maximum of cut
A²
1 to 64 000 000 KA²
MAX NBER OPERAT.
9999
Adjustment of maximum number of
circuit breaker operations
1 to 10000
RELAY C.B. FAULT
A B C D
Select relay to assign to the circuit
breaker failure function
See chap 4 to choose a relay or
to modify the assignment
RELAY C.B. FAULT
E F G
(D, E, F, G relay if option
available)
REL.L/R NO-COMPL
A B C D
Select relay to assign to no-
complementarity local/distant
function
(remote control in service)
REL.L/R NO-COMPL
E F G
(D, E, F, G relay if option
available)
NB OF INPUTS L/R
2 inputs
Number of input(s), configurable for
the management of the
Local/Remote mode
1 or 2 digital inputs
CONTROL CB POSIT
Inactive
Choose Active to use the
management of the CB position
Active or Inactive
CLOS. LOC. INPUT
No input
Display of input assigned to the
closing in local
(configurable with PC software)
No input, Input 1 to 8 (or 1 to 4
according option)