s. 22 / 40
Note: This menu is divided into 32 sections that refer to 32 possible logical steps STP1…STP32 which can be managed by the 8BGA.
P03.n.01
- Weight of step n, referred to the value of the smallest step. A number that indicates the multiple of the power of the current step with reference to the smallest set by
P02.07. If set to OFF the step is disabled and will not be used.
P03.n.02
- Type device delegated the insertion step.
Contactor = Switching with electromechanical contactor. On this step the time of reconnection is used.
Static = Electronic thyristor switching. On this step the time of reconnection is not considered . Used for Fast power factor correction.
M04 –MASTER OUTPUTS
(OUTn, n=1…16)
Psw
(M15)
UoM
Default
Range
P04.n.01
Output OUTn function
Adv
n=1…8
Step x
See
Output function table
n=9…16
OFF
P04.n.02
Channel number x
Adv
n=1…8
x=1…8
1 – 99
n=9…16
x=1
P04.n.03
Output normal/reversed
Adv
NOR
NOR
REV
Note: This menu is divided into 16 sections that refer to 16 possible digital outputs OUT1…OUT16, which can be managed by the master 8BGA; OUT81..OUT08 on the base
board and OUT09…OUT16 on any installed expansion modules.
P04.n.1
– Selects the functions of the selected output (see programmable chapter
25. Outputs functions table
).
P04.n.2
– Index associated with the function programmed in the previous parameter. Example: if the output function is set to
Step x
, and you want this output to be energized when
there is the step 10 insertion, then P04.n.02 should be set to value 10 or If the output function is set to
Alarm xx
, and you want this output to be energized for alarm A31,
then P04.n.02 should be set to value 31.
P04.n.3
- Sets the state of the output when the function associated with the same is inactive:
NOR
= output de-energized,
REV
= output energized.
M05 – MASTER / SLAVE
Psw
(M15)
UoM
Default
Range
P05.01
Master-Slave function
Usr
OFF
OFF
COM1
COM2
P05.02
Device role
Usr
Master
Master
Slave01
Slave02
Slave03
…
Slave08
P05.03
Slave 1 enable
Usr
OFF
OFF-ON
P05.04
Slave 2 enable
Usr
OFF
OFF-ON
P05.05
Slave 3 enable
Usr
OFF
OFF-ON
P05.06
Slave 4 enable
Usr
OFF
OFF-ON
P05.07
Slave 5 enable
Usr
OFF
OFF-ON
P05.08
Slave 6 enable
Usr
OFF
OFF-ON
P05.09
Slave 7 enable
Usr
OFF
OFF-ON
P05.10
Slave 8 enable
Usr
OFF
OFF-ON
For more information download the complete manual of the RPC 8BGA power factor controller from the web site
download area concerning the low voltage power
factor correction systems.
M06 – SLAVE 01 OUTPUTS
(n=1…16)
Psw
(M15)
UoM
Default
Range
P06.n.01
Output OUTn function
Usr
n=1…8
Step x
See
Output function table
n=9…16
OFF
P06.n.02
Channel number x
Usr
n=1…8
x=1…8
1 – 99
n=9…16
x=1
P06.n.03
Output normal/reversed
Usr
NOR
NOR
REV
For more information download the complete manual of the RPC 8BGA power factor controller from the web site
download area concerning the low voltage power
factor correction systems.
M13 – SLAVE 08 OUTPUTS
(n=1…16)
Psw
(M15)
UoM
Default
Range
P13.n.01
Output OUTn function
Usr
n=1…8
Step x
See
Output function table
n=9…16
OFF
P13.n.02
Channel number x
Usr
n=1…8
x=1…8
1 – 99
n=9…16
x=1
P13.n.03
Output normal/reversed
Usr
NOR
NOR
REV
See above, referred to slave 08
M14- PROGRAMMABLE INPUTS
(INPn, n=1…8)
Psw
(M15)
UoM
Default
Range
P14.n.01
INPn input function
Adv
OFF
(see Input functions table)
P14.n.02
Function index (x)
Adv
OFF
OFF / 1…99