Configuration with MV measurement and correction on LV side
CONFIGURATION WITH MV MEASUREMENT AND CORRECTION ON LV SIDE
Voltage measure
1 ph-to-ph voltage reading L2-L3 on MV side
Current measure
L1 phase
Phase angle offset
90°
Capacitor overload current measure
1 reading on L1-L3, LV side
Parameter setting
P02.03 = Three-phase
P02.04 = L1
P02.06 = L2-L3
P02.22 = LV/MV
P02.23 = ON