s. 20 / 40
work memory. The data backup 'copy' and 'restore' commands can be found in the commands menu.
(
see chapter 27. Command menu
)
21. Parameter table
Below are listed all the programming parameters in tabular form. For each parameter are indicated the
possible setting range and factory default, as well as a brief explanation of the function of the parameter.
The description of the parameter shown on the display can in some cases be different from what is
reported in the table because of the reduced number of characters available. The parameter code can be
used however as a reference.
Note:
The parameters shown in the table with a shaded background are essential to the operation of the system, thus they
represent the minimum programming required for operation.
M01 - UTILITY
Psw
(M15)
UoM
Default
Range
P01.01
Language
Usr
English
English
Italian
French
Spanish
Portuguese
German
Polish
Czech
Russian
Custom
P01.02
Set clock at system power on
Usr
OFF
OFF-ON
P01.03
LCD contrast
Usr
%
50
0-100
P01.04
Display backlight high intensity
Usr
%
100
0-100
P01.05
Display backlight low intensity
Usr
%
25
0-50
P01.06
Time to switch to low backlighting
Usr
s
180
5-600
P01.07
Return to default page
Usr
s
60
OFF / 10-600
P01.08
Default page
Usr
main
(page list)
P01.09
Plant description
Usr
(empty)
String 20 chr.
P01.01
– Select display text language.
P01.02
– Active automatic clock settings access after power-up.
P01.03
–
Adjust LCD contrast.
P01.04
–
Display backlight high adjustment.
P01.05
–
Display backlight low adjustment.
P01.06
– Display backlight low delay.
P01.07
–
Default page display restore delay when no key pressed. If set to OFF the display will always show the last page selected manually.
P01.08
– Default page displayed on power-up and after delay.
P01.09
– Free text with alphanumeric identifier name of specific panel/plant. If a description is set here, it will be shown as title of tha home page. The sme description will be used
also for identification after remote reporting alarms/events via SMS/E-mail.
M02 – GENERAL
Psw
(M15)
UoM
Default
Range
P02.01
CT primary
Usr
A
OFF
OFF/1-30000
P02.02
CT secondary
Usr
A
5
1
5
P02.03
Plant type
Usr
Three-ph
Three-phase
Single phase
P02.04
Current reading phase
Usr
L1
L1
L2
L3
L1 L2 L3
P02.05
CT polarity
Usr
Aut
Aut
Dir
Rev
P02.06
Voltage reading phase
Usr
L1-L2-L3
L1-L2
L2-L3
L3-L1
L1-N
L2-N
L3-N
L1-L2-L3
L1-L2-L3-N
P02.07
Smallest step power
Usr
kvar
1.00
0.10 – 10000
P02.08
System rated voltage
Usr
V
400
50 – 50000
P02.09
Rated frequency
Usr
Hz
Aut
Aut
50Hz
60Hz
Variable
P02.10
Reconnection time
Usr
s
60
1-30000
P02.11
Sensitivity
Usr
s
60
1-1000