Innovative Controls, Inc
Fire Pressure Governor User Manual
3050621, 3050622, 3050623, 3050624
Innovative Controls, Inc.
560 Braddock Avenue
East Pittsburgh, PA 15112
Page 29 of 32
Rev 1.10
Parameter
Number
Parameter
Name
Description
Default
Menu
Level
79
PRES HIGH
Configures the minimum discharge pressure
required before a “PRESSURE DROPPED”
alarm message is possible. Range is 50 to 250
PSI, adjustable in 5 PSI steps.
50 PSI
OEM
80
PRES LOW
Configures the discharge pressure threshold
under which the discharge pressure will turn on
the PRESSURE DROPPED alarm. Range is 30
to 250 PSI, adjustable in 5 PSI steps.
30 PSI
OEM
81
LOW INTAKE
Configures the LOW INTAKE alarm. Range is
ENABLED, DISABLED.
DISABLED
OEM
82
INT. P-THRES
Configures the intake pressure threshold. Range
is 0 to 50 PSI, adjustable in 5 PSI steps.
40 PSI
Service
83
INT. PRES L
Configures the intake pressure threshold under
which the intake pressure will turn on the LOW
INTAKE PRESSURE alarm. Range is 5 to 40
PSI, adjustable in 5 PSI steps.
20 PSI
Service
84
INT. TIMEOUT
Configures delay (in seconds) that the LOW
INTAKE PRESSURE alarm can be active before
Governor returns to IDLE MODE (0 disables
timeout). Range is 0 to 120, adjustable in 5
second steps.
0
Service
85
PSI IDLE
Configures the engine idle speed (RPM) for
pressure mode. Range is DISABLED, 600 to
900, adjustable in 25 RPM steps.
DISABLED
Service
86
RPM IDLE
Configures the engine idle speed (RPM) for
speed mode. Range is DISABLED, 600 to 900,
adjustable in 25 RPM steps.
DISABLED
Service
87
STAY IN MODE Configures the ability to remain in pressure or
speed mode until pump, throttle, or OK to pump
interlocks have been disengaged. This means
that alarm timeouts or pressing the idle button
will return the vehicle to idle speed, but the
Governor will remain in an active mode. Range
is ENABLED or DISABLED.
DISABLED
OEM