Parameter 

Number 

Parameter 

Name 

Description 

Default 

Menu 

Level 

58 

RPM MAX 

Sets the maximum speed of the engine in RPM. 

Range is 1500 to 3500 RPM, adjustable in 25-

RPM steps. 

3000 

OEM 

59 

POC ASSERT 

Sets the analog control mode power on value to 

the 0 or the idle value. Range is NO or YES.   

NO 

OEM 

60 

ANALOG IDLE 

Sets the analog control idle voltage. Each step 

value represents approximately 10 millivolts. 

Range is 0 to 60. 

32 

OEM 

61 

DITHER 

Enables or disables the +/- 5RPM speed 

dithering handshake (TSC1 only). Range is OFF 

or ON. 

OFF 

OEM 

62 

ECM MSG TX 

Enables or disables the Cummins engine control 

message when in idle mode. Range is NO TX @ 

IDLE, TX @ IDLE.  

NO TX @ 

IDLE 

OEM 

63 

CHASSIS 

Chassis, engine, and pump preset configuration. 

0 is no preset configuration. Range is 0 to 255. 

OEM 

64 

PRESS LIMIT 

Configures the maximum allowed pressure 

increase when in RPM mode. Range is 10 to 

100 PSI, adjustable in 5 PSI steps. 

30 

Service 

65 

RPM LIMIT 

Configures the minimum change in pressure 

expected (when in pressure mode) for an 

increase of 200 RPM in engine speed. Range is 

5 to 100 RPM, adjustable in 5 RPM steps. 

10 

Service 

66 

RPM TIMEOUT  Configures delay (in seconds) between “RPM 

LIMIT” detection and the application of the 

restriction/limit of setpoint in pressure mode. 

Range is 0 to 30, adjustable in 1 second steps. 

Service 

67 

H20 TIMEOUT 

Configures delay (in seconds) between 

“PRESSURE DROPPED” detection and the 

application of the restriction/limit of setpoint in 

RPM mode. Range is 5 to 120, adjustable in 5 

second steps. 

10 

Service 

68 

DECEL RATE 

Configures RPM deceleration rate to IDLE 

preset. Range is 200 to 2000 RPM, adjustable in 

100 RPM steps. 

500 

Service 

Содержание 3050621

Страница 1: ...Innovative Controls Inc Fire Pressure Governor User Manual 3050621 3050622 3050623 3050624 Innovative Controls Inc 560 Braddock Avenue East Pittsburgh PA 15112 August 13 2021 Rev 1 10...

Страница 2: ...erbiage throughout document to reflect updated governor design housing hardware and software 1 2 8 6 2020 Removed 125k from table 10 4 1 CAN specification 1 3 8 12 2020 Added section 1 3 16 modified d...

Страница 3: ...0 Braddock Avenue East Pittsburgh PA 15112 Page 3 of 32 Rev 1 10 Explanation of Symbols The exclamation mark within an equilateral triangle is intended to alert personnel applying this device to impor...

Страница 4: ...3 10 Pressure Mode Button 9 1 3 11 RPM Mode Button 9 1 3 12 Preset Button 9 1 3 13 Idle Button 10 1 3 14 Increment Decrement Buttons 10 1 3 15 Increment Decrement Knob with Idle Button 10 1 3 16 Stat...

Страница 5: ...ensor Dimensions 20 List of Tables Table 1 FPG Part Numbers 7 Table 2 FPG Interlock Inputs and Operating Modes 11 Table 3 Status Display Messages 13 Table 4 12 Pin Key A Connector 17 Table 5 6 Pin Con...

Страница 6: ...essure by adjusting the engine speed to keep the pressure at the operator s setpoint The engine speed high idle and idle ramp control modes all use the J1939 network to regulate the engine speed to th...

Страница 7: ...nel The FPG control switches indicators and displays are located on the front panel Refer to Figure 1 below The indicators can be configured to automatically adjust their brightness based on ambient l...

Страница 8: ...ump Engaged inputs are active or when the OK 2 Pump input is active and the configuration parameter is set to OK2PUMP 1 3 6 Engine Coolant Temperature Indicator The Engine Coolant Temperature Indicato...

Страница 9: ...w at 11 8VDC or less The battery voltage is measured directly at the FPG DC power input The battery voltage measurement has a configurable offset that can be used to handle voltage drops between the b...

Страница 10: ...nd 3050624 models of the FPG The direction the knob is turned to cause an increase in the setpoint value is configurable to be either clockwise or counterclockwise The rotary knob is also used to adju...

Страница 11: ...condition is enabled when both the Throttle Ready and Pump Engaged interlock inputs are active or when the FPG OK To Pump interlock input is active and the configuration parameter is set to OK2PUMP Th...

Страница 12: ...tions for operators and equipment Operators must follow their organization s standard operating procedures The FPG pressure mode regulates the pump discharge pressure regardless of the number of open...

Страница 13: ...an the critical range ENGINE TEMP Engine temperature is in warning or critical range ENGINE OIL Engine oil pressure is in warning or critical range TRANSMISSION TEMP Transmission temperature is in war...

Страница 14: ...5263 SPN 100 Displays no data when the SPN is not being received ENGINE OIL nnn F Engine oil temperature from J1939 PGN 65262 SPN 175 Displays no data when the SPN is not being received ENG COOLANT nn...

Страница 15: ...n The alarm output can be silenced for 1 minute by pressing the Status button on the knob version of the FPG or by pressing the active mode button on the pushbutton version of the FPG The operator can...

Страница 16: ...tification Figure 3 FPG Connectors The 12 Pin Key A connector is a Deutsch DT15 12PA that is common to all FPG models It mates with a Deutsch DT 06 12SA plug This connector interfaces with the vehicle...

Страница 17: ...alog Engine Control Negative Reference 10A PUMP ENGAGED Pump Engaged Interlock Input Active High 11A DELAY RELAY COM 30 Delay Relay Common Input 12A DELAY RELAY N O 87 Delay Relay Normally Open Output...

Страница 18: ...in Table 7 Detailed wiring diagrams are shown below in Figure 4 Table 7 Cable Assembly Part Numbers Description IC Part Number Cable Assembly FPG Power and CAN Interface Cable 4000675 01 Cable Assembl...

Страница 19: ...e pump discharge pressure sensor on the discharge manifold side of the pump Install the pump intake pressure sensors on the intake manifold side of the pump when applicable The pressure sensor 300 or...

Страница 20: ...0 psi Sealed Gauge or Absolute Male 1 4 NPT 0 5V to 4 5V Output 5V Supply 0 5 Accuracy Metri pack 150 Connector 3050473 30 To 600 psi Sealed Gauge or Absolute Male 1 4 NPT 0 5V to 4 5V Output 5v Suppl...

Страница 21: ...Preset and Status buttons for five seconds For models with buttons 3050621 and 3050622 press and hold the Preset and Idle buttons for five seconds Please refer to section 3 1 for more details Pressin...

Страница 22: ...ble in 1 PSI steps 5 User 8 ALLOW PRESET Enable or disable operation of speed mode preset button when pump pressure is greater than 10 PSI Range is NO or YES NO User 9 PRE PSI MIN Minimum pump dischar...

Страница 23: ...ressure Press PRESET to run the calibration routine NA Service 19 ENGINE TYPE Engine control type Range is CUMMINS FPG J1939 PGN0 SCANIA VOLVO MERCEDES ANALOG CUMMINS OEM 20 BRIGHTNESS Adjusts display...

Страница 24: ...increments 1 User 31 YEAR Sets the real time clock year Range is 2000 to 3000 adjustable in 1 year increments 2018 User 32 HOUR Sets the real time clock hour of the day Range is 0 to 23 adjustable in...

Страница 25: ...SOURCE ID Configures the CAN bus source address for the governor Range is 0 to 255 adjustable in 1 unit steps 7 OEM 42 OK TO PUMP Configures the OK TO PUMP interlock source from either the combination...

Страница 26: ...control mode Range is 0 to 10 adjustable in 1 unit steps 0 Service 50 SPEED P GAIN Adjusts the PID control loop Proportional gain in speed control mode Range is 0 to 100 adjustable in 1 unit steps 60...

Страница 27: ...O TX IDLE TX IDLE NO TX IDLE OEM 63 CHASSIS Chassis engine and pump preset configuration 0 is no preset configuration Range is 0 to 255 0 OEM 64 PRESS LIMIT Configures the maximum allowed pressure inc...

Страница 28: ...TROL MODE Configures the control modes allowed for use Options are PSI RPM PSI ONLY and RPM ONLY PSI RPM OEM 74 P TIME Configures sample rate in milliseconds ms for analog pressure control mode Range...

Страница 29: ...Service 83 INT PRES L Configures the intake pressure threshold under which the intake pressure will turn on the LOW INTAKE PRESSURE alarm Range is 5 to 40 PSI adjustable in 5 PSI steps 20 PSI Service...

Страница 30: ...ectrical Performance designed to meet CAN bus protected for heavy duty trucks 24V Transient voltage protected to SAE J1113 specification for heavy duty trucks 24V Load dump voltage protected to SAE J1...

Страница 31: ...mperature 40 C to 105 C Package Case Cylinder 4 3 Environmental Specifications The Innovative Controls Inc FPG environmental specifications are in the following table Table 12 FPG Environmental Specif...

Страница 32: ...echanical Specifications Parameter Specification Mechanical Performance designed to meet Resonance dwell SAE J1455 sec 4 9 4 1 Random vibration SAE J1455 sec 4 9 4 2 Mechanical shock SAE J1455 sec 4 1...

Отзывы: