Innovative Controls, Inc
Fire Pressure Governor User Manual
3050621, 3050622, 3050623, 3050624
Innovative Controls, Inc.
560 Braddock Avenue
East Pittsburgh, PA 15112
Page 27 of 32
Rev 1.10
Parameter
Number
Parameter
Name
Description
Default
Menu
Level
58
RPM MAX
Sets the maximum speed of the engine in RPM.
Range is 1500 to 3500 RPM, adjustable in 25-
RPM steps.
3000
OEM
59
POC ASSERT
Sets the analog control mode power on value to
the 0 or the idle value. Range is NO or YES.
NO
OEM
60
ANALOG IDLE
Sets the analog control idle voltage. Each step
value represents approximately 10 millivolts.
Range is 0 to 60.
32
OEM
61
DITHER
Enables or disables the +/- 5RPM speed
dithering handshake (TSC1 only). Range is OFF
or ON.
OFF
OEM
62
ECM MSG TX
Enables or disables the Cummins engine control
message when in idle mode. Range is NO TX @
IDLE, TX @ IDLE.
NO TX @
IDLE
OEM
63
CHASSIS
Chassis, engine, and pump preset configuration.
0 is no preset configuration. Range is 0 to 255.
0
OEM
64
PRESS LIMIT
Configures the maximum allowed pressure
increase when in RPM mode. Range is 10 to
100 PSI, adjustable in 5 PSI steps.
30
Service
65
RPM LIMIT
Configures the minimum change in pressure
expected (when in pressure mode) for an
increase of 200 RPM in engine speed. Range is
5 to 100 RPM, adjustable in 5 RPM steps.
10
Service
66
RPM TIMEOUT Configures delay (in seconds) between “RPM
LIMIT” detection and the application of the
restriction/limit of setpoint in pressure mode.
Range is 0 to 30, adjustable in 1 second steps.
1
Service
67
H20 TIMEOUT
Configures delay (in seconds) between
“PRESSURE DROPPED” detection and the
application of the restriction/limit of setpoint in
RPM mode. Range is 5 to 120, adjustable in 5
second steps.
10
Service
68
DECEL RATE
Configures RPM deceleration rate to IDLE
preset. Range is 200 to 2000 RPM, adjustable in
100 RPM steps.
500
Service