Innovative Controls, Inc
Fire Pressure Governor User Manual
3050621, 3050622, 3050623, 3050624
Innovative Controls, Inc.
560 Braddock Avenue
East Pittsburgh, PA 15112
Page 28 of 32
Rev 1.10
Parameter
Number
Parameter
Name
Description
Default
Menu
Level
69
COMPANY
Configures company name displayed at startup. Innovative
OEM
70
OBD
J1939
Configures the OBD to J1939 gateway protocol
(typically used only in Ford chasses). Options
currently available are NONE, 1939CM405A,
1939XR501A, 1939CM506AP, and
1939CM550AP.
NONE
OEM
71
FUEL LOW
Configures the fuel percentage at which the
FUEL LOW alarm is set. Range is 0% to 100%,
adjustable in 5% steps.
15%
Service
72
DEF LOW
Configures the DEF percentage at which the
DEF LOW alarm is set. Range is 0% to 100%,
adjustable in 5% steps.
15%
Service
73
CONTROL
MODE
Configures the control modes allowed for use.
Options are “PSI & RPM”, “PSI ONLY”, and
“RPM ONLY”.
PSI & RPM
OEM
74
P-TIME
Configures sample rate in milliseconds (ms) for
analog pressure control mode. Range is 10ms to
1000ms, adjustable in 10ms steps.
500ms
OEM
75
S-TIME
Configures sample rate in milliseconds (ms) for
analog speed control mode. Range is 10ms to
1000ms, adjustable in 10ms steps.
500ms
OEM
76
WARN. TRANS Configures the temperature above which the
transmission oil temperature will turn on the
transmission warning (yellow) lamp. Range is
140°F to 260°F, adjustable in 10°F steps.
230°F
OEM
77
CRIT. TRANS
Configures the temperature above which the
transmission oil temperature will turn on the
transmission critical (red) lamp. Range is 140°F
to 260°F, adjustable in 10°F steps.
250°F
OEM
78
DIS. P-THRES
Configures the discharge pressure threshold
under which the discharge pressure will turn on
the NO WATER alarm. Range is 15 to 250 PSI,
adjustable in 5 PSI steps.
15 PSI
OEM