The redundant ac-power switch FRU assembly includes the redundant ac-power switch and the input
power cables. They should all be replaced together.
These instructions assume that a redundant ac-power switch has been removed and the one or two nodes
that were connected to it are powered off.
To replace a redundant ac-power switch, complete the following steps:
1.
Attach each of the two mounting plates to the redundant ac-power switch using three M3 Torx T8
head screws. Position the mounting face, as shown in Figure 293, on the side of the redundant
ac-power switch that contains the output power sockets.
2.
Using the labels provided, label each end of the two redundant ac-power switch input power cables.
Unless the configuration is changing, the labels are the same as those on the cables removed with
the old redundant ac-power switch. Label the rack power distribution end “Power source
<name>
,
outlet
<id>
” to redundant ac-power switch
<location>
<MAIN | BACKUP>
input. For example: “Power
source D2, outlet 4 to redundant ac-power switch pos 7 MAIN input”.
3.
Label the redundant ac-power switch end“ redundant ac-power switch
<location>
<MAIN | BACKUP>
input from Power source
<name>
, outlet
<id>
”.
4.
Connect the input power cables to the redundant ac-power switch. You want to connect the cables
now, because it is difficult to access the input power sockets on the redundant ac-power switch
when it is installed in a rack.
5.
Connect the main input power cable to the redundant ac-power switch.
6.
Connect the backup input power cable to the redundant ac-power switch.
7.
Secure both the redundant ac-power switch input cables, as shown in Figure 294 on page 270, using
the clips of the redundant ac-power switch.
svc00294
Figure 293. Attaching the mounting plates
Chapter 2. Removing and replacing parts
269
Содержание SAN Volume Controller
Страница 1: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 Release 1 GC27 2226 03...
Страница 2: ......
Страница 3: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 Release 1 GC27 2226 03...
Страница 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 22: ...xx IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 26: ...xxiv IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 316: ...290 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 322: ...Taiwan Class A compliance statement 296 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 324: ...298 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 326: ...300 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 332: ...306 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 333: ......
Страница 334: ...Part Number 31P1173 Printed in USA GC27 2226 03 1P P N 31P1173...