Go to "Starting Problem Analysis" in topic 1.2.
17. Is *000 displayed on the Data display?
Yes No
Go to "Starting Problem Analysis" in topic 1.2.
End of procedure.
18. For those slots that have a serial number indicated in step 4 but do
not have a disk drive present, perform the following:
Can the disk drives with the serial numbers recorded in step 4 be
found?
Yes No
Go to step 24.
19. Warning: If these disk drives have been installed in another device
or system, data corruption may be present. Go to step 24 if you are
not sure about the data integrity of the disk drives.
Install the disk drives in the slots that match the serial numbers
recorded in step 4.
Note: Ensure that each disk drive is connected to the correct power
cable and signal cable. Also, ensure that the address jumper is
installed in the position shown and is only installed on disk drives
in odd-numbered slots (1, 3, 5, or 7).
20. Set the Power switch to the On position.
21. After 3 minutes, is *000, B000, or BBA0 displayed on the Data display?
Yes No
Go to "Starting Problem Analysis" in topic 1.2.
22. From your computer system, run the diagnostic test programs for the
3514/A Array Adapter. (See the 3514 Quick Reference Manual SA21-9613
for instructions on running diagnostics.)
Did the test programs run without error?
Yes No
Go to "Starting Problem Analysis" in topic 1.2.
23. Is *000 displayed on the Data display?
Yes No
Go to "Starting Problem Analysis" in topic 1.2.
End of procedure.
24. Can all the disk drives recorded in step 4 except one be found?
No Yes
Go to step 29.
25. Set the Power switch to the On position.
After 3 minutes, 3514CE27 will be displayed.
26. Using the control panel, set the 3514 offline by entering the
following sequence:
3514 Service Information
URC CE27
¦ Copyright IBM Corp. 1992, 1993
3.5.5.1 - 3