4 Ethernet or Token-Ring connection
The corresponding CHPID can be located using
“Locating the correct CHPID on the card.” on
page 6-36.
Note:
There are 2 LAN cable connector
types for each token-ring. An
RJ-45 or a 9 pin D-shell connect
only one.
1. Connect the correct Ethernet/Token-Ring
LAN cable (one for each adapter).
Note:
LAN cables are customer supplied.
The RJ-45 to 9 pin "D" shell
adapter (part 60G1066) will be
available for those customers that
need it and will not be shipped with
every adapter.
Do Not
remove wrap plugs from unused
adapters.
5 WAC connection
The corresponding CHPID can be located using
“Locating the correct CHPID on the card.” on
page 6-36.
Use the chart Table 6-2 on page 6-34 for the
plugging sequence.
The can be up to three WAC adapters if there are
no MPM2 adapters present.
1. If present connect the WAC cable to the
adapter(s)
6 MPM2 connection
The corresponding CHPID can be located using
“Locating the correct CHPID on the card.” on
page 6-36.
Use the chart Table 6-2 on page 6-34 for the
plugging sequence.
The can be up to two MPM2 adapters if there are
no more than one WAC adapter present.
1. If present connect the MPM2 cable to the
adapter(s)
Chapter 6. Completing the Installation
6-35
Содержание Multiprise 3000 S/390
Страница 1: ...S 390 Multiprise 3000 Enterprise Server R IBM Installation Manual SY24 6154 03...
Страница 2: ......
Страница 3: ...S 390 IBM Installation Manual SY24 6154 03...
Страница 8: ...vi Installing the System...
Страница 14: ...xii Installing the System...
Страница 34: ...1 20 Installing the System...
Страница 40: ...2 6 Installing the System...
Страница 78: ...5 20 Installing the System...
Страница 156: ...6 78 Installing the System...
Страница 160: ...7 4 Installing the System...
Страница 172: ...B 4 Installing the System...
Страница 173: ......
Страница 174: ...IBM Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY24 6154 3...
Страница 175: ...Spine information IBM S 390 Installation Manual...