Installing the support rails and rear brackets

Notes:

1.

For proper weight distribution, install the support rails as low in the rack cabinet as possible.

2.

The rack cabinet must have a minimum depth of 100 cm (40 in.).

To install the left and right support rails in the rack cabinet, complete the following steps. Use the front
and rear rack-mounting templates on pages 21 and 23 to align the support rails and rear brackets with
the correct rack holes. If the support rails will be installed above an existing storage subsystem or storage
expansion enclosure, position the EXP5060 support rails directly above it. If the support rails will be
installed below an existing storage subsystem or storage expansion enclosure, allow 178 mm (7 in.) of
vertical clearance for the EXP5060.

1.

Make sure that the rack has already been installed.

2.

Make sure that a stabilizer has been attached correctly to the bottom front of the rack to prevent the
rack from tipping forward while the storage expansion enclosure is being installed.
Refer to the installation and service guide, or equivalent, for the rack as required.

3.

Locate the two support rails, eight M5 screws, and eight washers that are supplied with the storage
expansion enclosure.

Note:

The screws and washers might already be attached to the support rails. If so, remove them
from the support rails.

4.

Starting with the left support rail, loosen the two rail adjustment screws with a medium flat-blade
screwdriver. The adjustment screws are used to lock the support rails at a certain length.

Note:

The support rails are not marked as left or right. However, each rail can be mounted correctly
on only one side of the rack cabinet. The rails should be mounted with the alignment pin at
the rear of the rack.

Front

Rear

Front rack
cabinet rail

Screws

Support
rail lip

Rail adjustment
screws

Rear rack
cabinet rail

Screws

5.

Hold the front of the left support rail against the inside of the front rack cabinet support flange, and
extend the rear of the support rail until it makes contact with the rear rack cabinet support flange.
The alignment pins at the rear of the support rail slide into the mounting holes at the rear of the
rack cabinet. The wider end of the support rail must be positioned at the front of the rack cabinet.

6.

From the front of the rack cabinet, with the support-rail flanges positioned inside the rack cabinet
support rail assemblies, insert two M5 screws with washers through the front of the cabinet and
screw them into the support rail front flange. Make sure that you use a washer when you install an
M5 screw through a square hole on a rack-mounting flange.

7

Содержание EXP5060

Страница 1: ...ar brackets on page 7 5 Installing and removing the handles on page 9 6 Installing the storage expansion enclosure in the rack cabinet on page 10 7 Installing the DDMs on page 12 8 Installing the cabl...

Страница 2: ...at they can handle the EXP5060 voltage and currents v Do not overload the power outlet when you install multiple devices in the rack cabinet v Install the storage expansion enclosure in a rack cabinet...

Страница 3: ...through the parts ordering system UPS Logistics is used to ship and return the lift tool Use the part number 09P2481 when you order the lift tool You must provide the following information when you or...

Страница 4: ...om the shipping box Do not remove the EXP5060 from the shipping box at this time v Box containing the mounting hardware kit v Six full or empty boxes of DDMs Note The DDMs are packaged ten per box The...

Страница 5: ...ight contain additional materials that are not shown in the following illustration Support rails Storage expansion enclosure M5 x 8 mm screws 16 Small Form factor Pluggable transceivers pre installed...

Страница 6: ...d in the support rails or packaged in a plastic bag Washers 8 Clip nuts 4 Important The EXP5060 does not ship with region specific ac power cords You must obtain the IBM approved power cords for your...

Страница 7: ...enclosure Note The screws and washers might already be attached to the support rails If so remove them from the support rails 4 Starting with the left support rail loosen the two rail adjustment scre...

Страница 8: ...lade screwdriver 10 Repeat steps 4 on page 7 through 9 for the right support rail Note Because the mounting holes on the rack are not always the same size as the mounting screws the lip of each of the...

Страница 9: ...tom of the handle in the opening in the storage expansion enclosure chassis and push the handle in and up until the latch at the top of the handle secures the handle to the chassis 3 Repeat step 2 for...

Страница 10: ...f the size and weight of the storage expansion enclosure as shipped a lift tool and a minimum of two trained service technicians are required to push the enclosure out of its custom designed package a...

Страница 11: ...Tighten all of the M5 screws to secure the rear of the storage expansion enclosure to the rack cabinet 8 Turn the rear bracket thumbscrews to attach the rear brackets to the sides of the storage expan...

Страница 12: ...e drive drawers are preinstalled in the EXP5060 but the DDMs are shipped separately from the drive drawers 2 Make sure that you install the storage expansion enclosure in the rack cabinet before you i...

Страница 13: ...front row of the drive drawer 6 Push the drive drawer into the storage expansion enclosure until it clicks and close the levers on each side of the drawer Attention Make sure you push both levers back...

Страница 14: ...nce Guide The EXP5060 is compatible with DS5100 and DS5300 storage subsystems The following cabling instructions are shown with the assumption that the EXP5060 will be connected to a DS5100 or DS5300...

Страница 15: ...procedures other than those specified herein might result in hazardous radiation exposure DANGER Some laser products contain an embedded Class 3A or Class 3B laser diode Note the following Laser radia...

Страница 16: ...he storage subsystem to port 1B on ESM B in EXP5060 one 4 Connect a fiber optic cable from drive port 6 on controller A in the storage subsystem to port 1B on ESM A in EXP5060 two 5 Connect a fiber op...

Страница 17: ...Some laser products contain an embedded Class 3A or Class 3B laser diode Note the following Laser radiation when open Do not stare into the beam do not view directly with optical instruments and avoi...

Страница 18: ...e from drive port 2 of controller B in the storage subsystem to port 2B on ESM B in EXP5060 one 6 Connect a fiber optic cable from drive port 6 on controller A in the storage subsystem to port 1B on E...

Страница 19: ...al cable for the rack PDUs for the voltage and currents that the EXP5060 requires If you do not have an IBM System Storage 2101 200 rack with the supported PDUs and 60 A power cords check your PDUs or...

Страница 20: ...Under Support downloads click the applicable support category Note For detailed information about device driver and firmware versions make sure that you read the readme files that are posted with each...

Страница 21: ...1U 0U 0U Rail assembly front left Rail assembly front right FRONT Rack Mounting Template 4U 4U Install second Install first Install second Install first Install first Install first Install second Ins...

Страница 22: ...22...

Страница 23: ...3U 3U 2U 2U 1U 1U 0U 0U Rail assembly rear left Rail assembly rear right Printed in the U S A REAR Rack Mounting Template Rail mounting guide 4U 4U Rear bracket Rear bracket 23...

Страница 24: ...s other countries or both Microsoft and Windows are trademarks of Microsoft Corporation in the United States other countries or both Copyright International Business Machines Corporation 2009 US Gover...

Отзывы: