Verifying Controller Module Operation
To verify Controller module operation:
1. Press the LED test button and check that all LEDs illuminate. Then release the LED test button.
Repeat for the second Controller module if two are installed.
2. Check the STBY (Standby) and Active LEDs.
If one Controller module is installed, check:
a. that the STBY LED is off
b. that the Active LED is on
c. that the Power Supply LED is on for each power supply unit installed
d. that the FAN LEDs are on
e. that the Temperature LED is off.
If two Controller modules are installed, check:
– that the Active LED on the active Controller module is on.
– that the STBY LED on the active Controller module is off.
– that the Active LED on the standby Controller module is off.
– that the STBY LED on the standby Controller module is on.
If any of the LEDs fail the above checks, refer to Table 8 on page 55.
Figure 20 shows the location of the LEDs on the Controller module front panel.
POWER
SUPPLY
Power Supply LEDs
Active LED
Temperature LED
Standby LED
LED Test Button
Reset Button
Fan 1 LED
Fan 2 LED
Fan 3 LED
Power Supply LEDs
1
1
2
2
3
3
8000-RCTL
4
FA
N
ACTIVE
TEMP
LED
TEST
HUB
RESET
STBY
Figure 20. 8265 Controller Module LEDs
For troubleshooting information, refer to page 55.
50
IBM 8265: Installation Guide
Содержание 8265 Nways ATM Switch
Страница 1: ...8265 Nways ATM Switch IBM Installation Guide SA33 0441 02...
Страница 2: ......
Страница 3: ...8265 Nways ATM Switch IBM Installation Guide SA33 0441 02...
Страница 8: ...vi IBM 8265 Installation Guide...
Страница 10: ...viii IBM 8265 Installation Guide...
Страница 12: ...x IBM 8265 Installation Guide...
Страница 14: ...xii IBM 8265 Installation Guide...
Страница 32: ...18 IBM 8265 Installation Guide...
Страница 52: ...38 IBM 8265 Installation Guide...
Страница 68: ...54 IBM 8265 Installation Guide...
Страница 88: ...Models 17S Serial Number Located on the 8265 chassis label 74 IBM 8265 Installation Guide...
Страница 98: ......
Страница 101: ......
Страница 102: ...IBM SA33 441 2...