4.3.22 Group H Screen 2
‘Group H Screen 2’ screen panel comes out when UP (
) button or DOWN button (
) in ‘Group
H Screen 1’ screen panel is touched. P gain and I gain of current/speed for vector control and
vectorless control are set in this screen panel. And rated capacity, rated current, rated voltage, and
no-load current of the motor are set in this screen panel, too.
Figure 29 Group H screen 2
When touching any button in the sreen panel, 10KEY screen comes out for inputting values. (Refer
to [Input way of 10KEY screen]).
(1)
Current P gain: set P gain of the current controller for vector control or sensorless vector control.
(2)
Current I gain: set I gain of the current controller for vector control or sensorless vector control.
(3)
Speed P gain: set P gain of the speed controller for vector control or sensorless vector control.
(4)
Speed I gain: set I gain of the speed controller for vector control or sensorless vector control.
(5)
Rated motor capacity: set the rated motor capacity in [MVA] unit.
(6)
Rated motor current: set the rated motor current in [A] unit.
(7)
Rated motor voltage: set the rated motor input line voltage in [kV] unit.
(8)