(2) Inverter READY signal: After receiving inverter MODE signal, inverter senses the conditions of
controlling power and trip state and sends inverter READY signal to DCS.
(3) External RESET when inverter TRIP: When self-TRIP is occured, operator can cancel the TRIP
by pushing RESET switch (RS1) in input VCB board after resolving the reasons of TRIP.
(4) External inverter RUN: When K2 VCB of output VCB board is closed, inverter runs by inverter
RUN.
(5) Inverter S operator signal by external signal: If DCS sends inverter stop signal, output VCB
board takes that signal and sends S operator signal to the inverter. Inverter is stopped by this
signal. After stopping, signal that opens K2 VCB of output VCB board is delievered.
4.3 Touch panel operator
N5000 inverter sets operational mode by using touch screen operator in front inverter panel.
(touch operator: operator). It performs operation monitoring, inverter constant value change, and
inverter control constant value change.
4.3.1 Operator hardware
1) Operator dimension
Operator dimension is shown in figures below.
Figure 1. Front dimension