4.3.15 Group B Screen 2
‘Group B Screen 2’ screen panel comes out when DOWN (
) button in ‘Group B Screen 1’ screen
panel. Configureations for data management and operation of the main controller are set in this
screen panel.
Figure 22 Group B screen 2
When touching any button in the screen panel, 10KEY screen comes out for inputting values.
(1)
Soft LOCK: Stop modifying data.
(2)
Initialization: Return the currently set values to initial values. Also clears the history of
functional failures and warings. But, accumulated operating time and power-on time are not
initialized.
0: [Displays ‘NON’] No initialization.
1: [Displays ‘Trip’] Initializes history of system failures and warnings.
2: [Displays ‘Para’] Initializes set values (parameters).
3: [Displays ‘TIME’] Initializes time.
4: [Displays ‘All’] Initializes all.
(3)
Cell bypass: Enables cell bypass function that make derating operation start.
0: [Displays ‘OFF’] when the cell is broken, it motors inverter FREE RUN.
1: [Displays ‘ON’] when the cell is broken, cell bypass function enables derating.
(4)
Protection: Cancels some protective functions that interrupt normal functional tests.
0: [Displays ‘OFF’] Normal protection is running.
1: [Displays ‘ON’] Cancels some protective functions for normal functional test.
(5)
CELLs per phase: Sets the number of cells for one phase. 3300V or 6600V is always the input
voltage for N5000 inverter. When 3300V is the input voltage, set it 3 in this item. When 6600V
is the input voltage, set it 6 in this item.
(6)
Controller mode: If 1 MCU board consists main controller, set it 1. (Displays ‘single’). If 2 MCU
Protection