InstallatIon
3-44
HPR130XD Auto Gas –
806330
Note: Cable AWG recommendations taken from table 310-16 of the National Electric Code handbook (USA).
Input voltage
Phase
Rated
input current (FlA)
@ 19.5 kw output
Recommended
time delay,
high inrush
fuse size
Recommended cable
size for 15 m (50 feet)
maximum length
Rated for 60° c (140° F)
200/208 vAc
3
62/60 A
85 A
26.7 mm
2
(3 AWG)
220 vAc
3
57 A
85 A
26.7 mm
2
(3 AWG)
240 vAc
3
52 A
65 A
21.2 mm
2
(4 AWG)
380 vAc
3
33 A
40 A
8.3 mm
2
(8 AWG)
400 vAc
3
32 A
40 A
8.3 mm
2
(8 AWG)
415 vAc
3
32 A
40 A
8.3 mm
2
(8 AWG)
440 vAc
3
28 A
35 A
8.3 mm
2
(8 AWG)
480 vAc
3
26 A
35 A
8.3 mm
2
(8 AWG)
600 vAc
3
21 A
30 A
5.3 mm
2
(10 AWG)
Power requirements
general
All switches, slow-blow fuses and power cables are customer-supplied and must be chosen as outlined by applicable
national and local electrical codes. Installation must be performed by a licensed electrician. Use a separate, primary, line
disconnect switch for the power supply. Recommendations on fuse and circuit breaker sizing are listed below, however
actual sizes required will vary based on individual site electrical line conditions (including but not limited to source
impedance, line impedance, and line voltage fluctuation), product inrush characteristics, and regulatory requirements.
The main feed protection device (Circuit Breaker or Fuse) must be sized to handle all branch-feed loads for both inrush
and steady-state current. The power supply must be wired into one of the branch-feed circuits. The power supply has
a steady-state current listed in the table below.
Use a motor-start circuit breaker or equivalent if time delay high inrush fuses are not permitted by local and national
codes. Time delay fuses and circuit breakers must be capable of withstanding inrush current that is up to 30 times the
rated input current (FLA) for 0.01 seconds and up to 12 times the rated input current (FLA) for 0.1 seconds.
Содержание HyPerformance HPR130XD
Страница 1: ...HyPerformance Plasma HPR130XD Auto gas Instruction manual 806330 Revision 3 ...
Страница 16: ...Table of Contents viii HPR130XD Auto Gas 806330 ...
Страница 26: ...Specifications 2 2 HPR130XD Auto Gas 806330 ...
Страница 38: ...Specifications 2 14 HPR130XD Auto Gas 806330 ...
Страница 48: ...Installation 3 10 HPR130XD Auto Gas 806330 ...
Страница 51: ...Installation HPR130XD Auto Gas 806330 3 13 LHF mounting Horizontal RHF mounting Vertical RHF mounting ...
Страница 59: ...Installation HPR130XD Auto Gas 806330 3 21 1X1 J103 J300 Female Male 5 6 5 6 3X1 3X2 3X3 3X4 ...
Страница 61: ...Installation HPR130XD Auto Gas 806330 3 23 7 Caution Never use PTFE tape on any joint preparation ...
Страница 94: ...Installation 3 56 HPR130XD Auto Gas 806330 ...
Страница 101: ...Operation HPR130XD Auto Gas 806330 Revision 2 4 7 Diagnostics screen ...
Страница 102: ...Operation 4 8 HPR130XD Auto Gas 806330 Revision 2 Test screen ...
Страница 103: ...Operation HPR130XD Auto Gas 806330 Revision 2 4 9 Cut chart screen ...
Страница 152: ...Operation 4 58 HPR130XD Auto Gas 806330 Revision 2 ...
Страница 236: ...7 4 HPR130XD Auto Gas 806330 Discrete output functionality ...
Страница 294: ...Appendix B CNC Interface Protocol b 28 HPR130XD Auto Gas 806330 Revision 1 ...
Страница 302: ...4 HPR130XD Auto Gas 806330 ...