InstallatIon
3-6
HPR130XD Auto Gas –
806330
Recommended grounding and shielding practices
Introduction
types of grounding
grounding practices
Recommended grounding and shielding practices
wARNINg!
ElEctRIc SHock cAN kIll
Disconnect electrical power before performing any maintenance.
All work requiring the removal of the plasma system cover must be performed by a
qualified technician.
See the
Safety
section of your manual for more safety precautions.
Introduction
This section describes practices for grounding and shielding to protect a plasma cutting system against radio frequency
interference (RFI) and electromagnetic interference (EMI) (also called
noise
). It also describes the DC power ground
and the service ground. The diagram at the end of this section shows these types of grounds in a plasma cutting
system.
Note:
The grounding practices in this section have been used on many installations with excellent results, and
Hypertherm recommends that these practices be a routine part of the installation process. The actual
methods used to implement these practices may vary from system to system, but should remain as
consistent as possible. However, due to the variation in equipment and installations, these grounding
practices may not succeed in every case to eliminate RFI/EMI noise issues.
types of grounding
Service ground
(also called safety ground or potential earth (PE) ground) is the grounding system that applies to the
incoming line voltage. It prevents a shock hazard to any personnel from any of the equipment or the cutting table. It
includes the service ground coming into the plasma system and other systems such as the CNC and the motor drives,
as well as the supplemental ground rod connected to the cutting table. In the plasma circuits, the ground is carried from
the plasma system chassis to the chassis of each separate console through the interconnecting cables.
Dc power ground
(also called cutting current ground) is the grounding system that completes the path of the cutting
current from the torch back to the plasma system. It requires that the positive lead from the plasma system be firmly
connected to the cutting table ground bus with a properly sized cable. It also requires that the slats, on which the
workpiece rests, make firm contact with the table and the workpiece.
RFI and EMI grounding and shielding
is the grounding system that limits the amount of electrical noise emitted by
the plasma and motor drive systems. It also limits the amount of noise that is received by the CNC and other control
and measurement circuits. The grounding practices described in this section mainly target RFI and EMI grounding
and shielding.
grounding Practices
1. Unless noted, use only 13.3 mm
2
(6 AWG) welding cables (047040) for the EMI ground cables shown on the
diagram at the end of this section.
2. The cutting table is used for the common, or star, EMI ground point and should have threaded studs welded
to the table with a copper bus bar mounted on them. A separate bus bar should be mounted on the gantry
as close to each motor as possible. If there are motors at each end of the gantry, run a separate EMI ground
Содержание HyPerformance HPR130XD
Страница 1: ...HyPerformance Plasma HPR130XD Auto gas Instruction manual 806330 Revision 3 ...
Страница 16: ...Table of Contents viii HPR130XD Auto Gas 806330 ...
Страница 26: ...Specifications 2 2 HPR130XD Auto Gas 806330 ...
Страница 38: ...Specifications 2 14 HPR130XD Auto Gas 806330 ...
Страница 48: ...Installation 3 10 HPR130XD Auto Gas 806330 ...
Страница 51: ...Installation HPR130XD Auto Gas 806330 3 13 LHF mounting Horizontal RHF mounting Vertical RHF mounting ...
Страница 59: ...Installation HPR130XD Auto Gas 806330 3 21 1X1 J103 J300 Female Male 5 6 5 6 3X1 3X2 3X3 3X4 ...
Страница 61: ...Installation HPR130XD Auto Gas 806330 3 23 7 Caution Never use PTFE tape on any joint preparation ...
Страница 94: ...Installation 3 56 HPR130XD Auto Gas 806330 ...
Страница 101: ...Operation HPR130XD Auto Gas 806330 Revision 2 4 7 Diagnostics screen ...
Страница 102: ...Operation 4 8 HPR130XD Auto Gas 806330 Revision 2 Test screen ...
Страница 103: ...Operation HPR130XD Auto Gas 806330 Revision 2 4 9 Cut chart screen ...
Страница 152: ...Operation 4 58 HPR130XD Auto Gas 806330 Revision 2 ...
Страница 236: ...7 4 HPR130XD Auto Gas 806330 Discrete output functionality ...
Страница 294: ...Appendix B CNC Interface Protocol b 28 HPR130XD Auto Gas 806330 Revision 1 ...
Страница 302: ...4 HPR130XD Auto Gas 806330 ...