Page 25
4.8
Atomisation Output
The atomisation output [kg/h] is dependent on
the atomisation air pressure set by the control unit and the water
pressure set by the vacuum valve.
4.8.1
Output Table
The output table below indicates the atomisation output of the
VN nozzles. Atomisation output depends on the water pressure
set by the vacuum valve and the atomisation air pressure set by
the control unit. These settings simultaneously influence droplet
size (see 4.8.2).
Note:
When setting the atomisation output, please allow for pre-
vailing environmental conditions such as temperature and clea-
rances from other objects.
Note:
Verify that the atomised water can be absorbed by the
surrounding air.
Note:
Note any overall pressure loss and air leakage related to
the design and installation of the air compressor.
humidification out put [kg /h]*
A tomis ation air pres sure s et by control unit [bar]
At omiz atio n air pres sure s et by control unit [ bar]
3
4
5
6
7
8
Sett ing
0,1
2 ,5
4,5
5,5
6,5
7 ,0
8,0
w ater press ure
0,3
2 ,5 4,0 4,5 6, 0 6 ,5 7,5
in 0,5
2 ,0
3,5
4,5
5, 5
6 ,0 7,0
vac uum v alv e
0,7
2
2,5
4,0
4, 5
5 ,5 6,5
[bar] 0,9
< 2,0
2,0
3,5
4, 5
5 ,0 6,0
1,1
< 2,0
< 2,0
2,5
4, 0
4 ,5 5,5
com press ed air
usa ge
[l/min]
20 25 30 35 40 45
*Av erage v alue ± 20%
Grey = rec ommende d ran ge
finer droplets
fine
r droplets
Содержание CU-1
Страница 1: ...Atomising Vacuum Nozzle System Manual...
Страница 37: ...Page 37 5 4 Example of Installation Fig Example of installation a VN Unit with 4 nozzles...
Страница 38: ...Page 38 Fig Example of installation a VN Unit with 8 VN nozzles and 2 vacuum valves...
Страница 48: ...Page 48 10 EC Declaration of Conformity...
Страница 54: ...Page 54 General 39 Water Installation 39 Wiring Diagram 42...