SPA
Page 81
14. Terminal Assignments on the Unit Con-
nector Strip and Wiring Diagram Legend
Unit Connector Strip:
Terminals
Assignment
1 / 2
Remote Switch / Safety Interlock
6 / 7
Temperature Sensor
8 / 9 / 13
Essence Injector max. 70 W / 24 V / 3.15 A
10 / 11
Exhaust Fan max. 40 W / 24 V / 1.6 A
10 / 12
Supply Fan max. 40 W / 24 V / 1.6 A
14 / 15
Light max. 40 W / 24 V / 1.6 A
Wiring Diagram Legend:
Designation Specification
B1
Max.-Water Level Electrode
B3
Transducer
F1 and F2
Fuses transformer (T1) 0.5 A or 1.0 A
F3 and F4
Fuses control 5.0 A
F5
Fuse transformer (T2, sensor electrode)
F7 and F8
Fuses transformer (T2, steam bath option) 0.5 A
or 1.0 A
F9 and F10
Fuses 5.0 A
F13
Essence Injector Fuse 2.5 A
F14
Exhaust Fan Fuse 1.6 A
F15
Supply Fan Fuse 1.6 A
F16
Light Fuse 1.6 A
K1
Main Contactor
L1 - L3
Main Terminals
M1
Blow-Down Pump
N
Neutral
PE
Grounding Terminal
S1
Control Switch ON (I) / OFF (0), pumping (II)
X1
Connector Strip
Y1
Solenoid Valve
Y2
SUPER FLUSH (optional)