Jumper I
The standard setting for this jumper is open.
This jumper must not be set or only be set after consultation with
HygroMatik.
Jumper J
The standard setting for this jumper is open.
This jumper must not be set or only be set after consultation with
HygroMatik.
Jumper K
The standard setting for this jumper is open.
This jumper must not be set or only be set after consultation with
HygroMatik.
Jumper L
The standard setting for this jumper is open.
This jumper must not be set or only be set after consultation with
HygroMatik.
Jumper E and J inverted
After a preprogrammed number of switching operations of the main
contactor (K1), the HygroMatik control provides the message "Mainte-
nance K1" indicated by the green LED rapidly flashing. The message
may be reset (after changing the main contactor) by inverting the
jumper E and J settings and, consequently, re-establishing the former
status again. To do so, please turn off the unit and reverse the E and J
jumper conditions, i.e. a jumper set must be removed and an open
contact must be jumpered. Following this, turn on the unit for about 5
seconds. Then turn off the unit again and re-establish the preceding
status of the jumpers. This resets the message.
Please note
Please note
Please note
Please note