9.2.1 Connection for Essence Injector with 24V Peri-
staltic Pump Type EP24 (Optional)*
The DS-Control only controls the essence injector when Parameter D2
= On has been selected.
Wire connection cable from the peristaltic pump to the steam generator
to terminals 8, 9 and 13 (s. schematic diagram below). The EP24 peri-
staltic pump is protected by a 2.5 A micro fuse. Maximum contact load
is 75W.
*: not valid for steam generators type C01 and C02
9.3 Fan Installation (Optional)
In any steam bath, an exhaust fan
(10) (s. also section „Steam
Bath Installation (Schematic Layout)“)
should be installed. The fan
removes warm air from the steam bath in order to ensure continuous
steam supply and stable temperature control.
Depending on the configuration of the steam bath, an air supply fan (8)
may also be operated.
In the steam bath, the exhaust fan should be installed:
•
high up and
•
across from the air supply vent
In the steam bath, the supply fan should be installed:
•
down low and across from the exhaust vent
Please note
Peristaltic Pump
EP24
(24V)
24V
N
24V
24V
Im
puls
PE
brown
black
grey
Steam
generator
8
13
9
Connection diagram for HygroMatik peristaltic pumps type: EP24 (24V)
M
Peristaltic Pump EP24
(8)
(10)