SPA
Page 78
X X
Lost Ground Con-
trol
•
Communication between main board and
display is disturbed
•
•
Check cable between mainboard
and display
Check RS485 interface
modules
X
Maintenance
The system
switches off after
60 min. in opera-
tion in cylinder full
condition.
•
Unit requires maintenance:
- Cylinder full of scale deposits wich limit the
electrodes immersion depth.
- Electrodes worn out.
•
•
Clean steam cylinder and elec-
trodes or replace electrodes.
Replace electrodes. (If electrode
wear is high, see note in section
„Electrode Exchange“ in unit hand-
book)
•
Phase defective (external fuse faulty).
•
Replace fuse.
•
With very low water conductivity continuous
steam production is insufficient in order to
concentrate and raise the water conductivity.
•
Establish water values and/or con-
tact HygroMatik about the problem.
X X
Maintenance K1
The system still op-
erates. The green
LED flashes rapid-
ly.
•
According to manufacturer specification 90%
of the electrical lifetime is achieved. To avoid
failure, a replacement of the main contactor is
recommended in the short term.
•
•
Replace main contactor.
See parameter description "P11 re-
set main contactor interval" for
Comfort / Comfort Plus control or
"Brief Description of Jumpers" for
Basic control..
X X
Safety stop
•
Parameter D5 for limitation of operating time
is activated. The steam generator stopped
operation after the safety interlock has been
closed for the time programmed under
parameter D5.
•
By opening and closing the safety
interlock the steam generator
restarts operation for the pro-
grammed hours (D5).
Alternatively set parameter D5 to 0
and restart system. The function
„limitation of operating time” is
deactivated.
HL
**
*
Hy
,C
**
*
Possible Condi-
tions
Probable Cause for fault situation
Resolution
X X
Water is collecting
on the base plate
•
Zylinder nach der Wartung falsch zusam-
mengebaut:
-
O-Ring beschädigt, nicht getauscht oder
nicht eingesetzt
-Flansch (Nut/Feder) beschädigt
-Flansch nicht richtig verschlossen
-Härtebildner im Flansch
•
Clean cylinder and install properly.
•
The cylinder is incorrectly placed on the base.
•
Lay a moistened new o-ring in the
base and then insert the cylinder.
•
The water cannot drain away during flushing.
•
Make sure drain is unobstructed.
LED Dis-
play
H
L
***
H
y
,C***
Message / Mal-
function Dis-
played*
Probable Cause
Resolution