6.
Parameters
6.1
Summary Table of Parameters
Para-
meter
Designation
Possible Settings
in Menu / Submenu
Access
Code
A4
Standby Blow-down
0 Min. - 999 Hours[ HHH : MM
]
Parameter Setting/Blow-
Down Parameters
none
A17
Stand-By heating
No/Yes
Start-up/System settings
010
C16
Interval time A17
0 - 999 min.
Settings/Power Parame-
ter
010
C17
On time A17
0 - 255 sec.
Settings/Power Parame-
ter
010
D0
Steam bath mode
“with status” / “without status” Parameter Setting/Steam
Bath Parameters
010
D1
Exhaust fan
Exhaust Fan Automatic / Con-
tinuous Operation
Parameter Setting/Steam
Bath Parameters
010
D2
Essence (injection)
Essence Injection Automatic /
off
Parameter Setting/Steam
Bath Parameters
010
D3
Light
Light on/off
Parameter Setting/Steam
Bath Parameters
010
D4
Supply fan
Supply Fan Automatic / Con-
tinuous Operation
Parameter Setting/Steam
Bath Parameters
010
D5
limitation of operating
time
0 - 255 h(0 is Factory setting
(=off))
Parameter Setting/Steam
Bath Parameters
010
E1*
Xp-PI-controller=100/
E1[Amplification]
0 - 100 %
Parameter SettingsControl
Parameters
010
E2*
Tn-PI-controller[Integra-
tion time]
0 - 255 sec.
Parameter SettingsControl
Parameters
E5
Base relay
(programmed switching
signal)
0= collective fault (
Factory
Setting
)
1= Fault Data Exchange
2= Humidification
3= Stand-By
4= Max. Level
5= Blow-Down Fault
6= Maintenance Interval
Expired
7= Fault Filling
8= No Demand
9= ----
10= ----
11= Activated Thermo Sensor
12= Fault Main Contactor
13= Supply Fan
14= Exhaust Fan
15= Essence Injection
16= Light
17= Super Flush
18= Maintenance
19=
Master: def.
20= Maintenance K1
Parameter Setting/
Data Parameters
010
E6
1. Transmitting relay
same options as with E5, sta-
tus 15 = factory setting
Parameter Setting / Data
Parameters
010