Switch/Safety Interlock
The steam generator is only operative when terminals 1 and 2 are
bridged. In case of neither a remote switch nor a safety device wired
across terminals 1 and 2, a wire bridge must be inserted.
The steam generator is only allowed to start operation if the contact
between terminal 1 and 2 is closed. If neither a remote switch nor a
safety device are wired to terminal 1 and 2, a wire bridge must be
installed.
Factory setting has no wire bridge across terminals 1 and 2.
For switching the HygroMatik steam generator on and off remotely, a
remote switch is to be connected across terminals 1 and 2. With the
switch closed the steam generator is operative. When opening the con-
tact across terminals 1 and 2, the steam generator ceases operation.
The wire loop across terminals 1 and 2 is used for safety interlock.
Safety devices such as an emergency shut-off switch or a max.-ther-
mostat may be wired in here.
Risk of scalding due to steam overheating in cabin caused by
temperature sensor failure!
Installation of a max-thermostat in the saftey interlock is strongly
recommended.
If both a circuit protection device and a remote switch are to be used,
wiring is in series.
Please note
Remote switch
Safety interlock
Safety interlock
and
Remote switch
Safety device
Humidifier terminals
Humidifier terminals
Safety device
Remote switch