Connection with 230V Peristaltic Pump type EP230
*
Lay the connection cable from the peristaltic pump to the steam gener-
ator at terminals 17, 18 and 19 (with a 230 V peristaltic pump, see con-
nection schematic above). The peristaltic pump is protected by the
1.6A main fuse of the steam generator.
Connection with 24V Peristaltic Pump Type EP24*
Lay the connection cable from the peristaltic pump to the steam gener-
ator at terminals 8, 9 and 13 (24 V peristaltic pump, see connection
schematic above). The peristaltic pump is protected by a 2.5 A micro
fuse.
*: not valid for steam generators type C01 and C02
Connection with 230V Peristaltic Pump type EPlogic
with own control logic (option)
The peristaltic pump type EPlogic is separately supplied with a voltage
supply of 230 / 240VAC, 50 / 60Hz. The parameters for dosing and
interval time can be changed on the display and control unit of the
peristaltic pump.
The peristaltic pump EPlogic receives the release for dosing from the
steam generator according to the following electrical connections:
release, potential free
terminal
steam generator
25
27
peristaltic pump
EPlogic
13
14
Peristaltic Pump EP230
Peristaltic Pump EP24
Peristaltic Pump EPlogic