background image

IGSV-ASCS-0303

10

Humidity System (cont.)

purge the line to flush any debris that may clog the water
filter. If the water line requires purging after the cases are
hooked together, it is not necessary to check each one.
Simply shut ball valves to each humidity system, remove
the water line from the last case in the flow, and purge. By
doing this as a precautionary measure, you may avoid
problems and repeat servicing.

START-UP

Turn on the fan circuit. Check to see if the fan for the
humidity system is running. Remove the right hand bottom
pan (when facing the front of the case), then the TXV cover.
The fan is located up against the right hand side of the
case, as viewed from the front, under the fan plenum (see
diagram). View the blade, and make sure the fan rotation
agrees with the air flow arrows. Turn on the water, by
turning the ball valve in the direction of the flow (OFF is
at 90° to the direction of flow).
After a few minutes, check the spray header by sliding the
honeycomb to the left to expose the discharge tube located
on the right hand side of the case (when viewed from the
rear), by lifting the 4'-0" section of honeycomb with both
ends, until the bottom clears. Pull up and set aside. The
spray header will be exposed. Grasp the header and pull it
loose from the 90° “L” until you see the misting nozzle,
which should be spraying. If not, check the following:

1. Make sure the water is feeding the nozzle.
2. Remove the nozzle, and purge the water.

3. Check strainer at entrance to nozzle.

Reinsert the header into the 90° “L”, making sure that the
nozzle is in the center of the pipe when totally inserted,
and the holes in the header are facing the front of the case
at a level angle.
The discharge tube can easily be pulled to service.

MAINTENANCE

Clean humidity system a minimum of every 90 days for
proper system operation.

HAGO-M1 NOZZLE
225-01-3221

WATER

SUPPLY

SPRAY HEADER

RUNS LENGTH OF CASE

WATER FILTER

3 STAGE #00015

225-01-2026

3" AXIAL FAN

225-01-2026

2ND FAN USED

IN 12' CASE

REAR INTERIOR WALL OF CASE

VIEWED FROM FRONT

BALL VALVE

HAMMON

225-01-2026

1/4" 100 X 1/8FPT
SW ADAPTER
225-01-2089A

1/4" OD X 1/8" FPT

SW ADAPTER

225-01-3059

1/8" MPT X 1/4" COMP

PVC ADAPTER

225-01-3059

1/4"MPT X 1/4" COMP PVC ADAPTER

225-01-2026

1/4"MPT X 1/4" OD

COMP ADAPTER

225-01-1312

PAN AND ACCESS PANEL

1/8" 100 X 1/8FPT
SW ADAPTER
225-01-3220

HUMIDITY SYSTEM as viewed from the front.
Note: The axial fans included in the humidity system must be
replaced as a unit.

Refrigeration

REFRIGERANT TYPE

The standard refrigerant will be R-22 unless otherwise
specified on the customer order. Check the serial plate
on the case for information.

PIPING

The refrigerant line outlets are located under the case.
Locate first the electrical box, the outlets are then on the
same side of the case, but at the opposite end. Insulate
suction lines to prevent condensation drippage.

REFRIGERATION LINES

 LIQUID

SUCTION

1/2"  O.D.

 5/8" O.D.

NOTE: The standard coil is piped at 5/8" (suction); however,

the store tie-in may vary depending on the number of
coils and the draw the case has. Depending on the case
setup, the connecting point in the store may be

5

/

8

", 

7

/

8

", or 1

1

/

8

". Refer to the particular case you are

hooking up.

Refrigerant lines should be sized as shown on the
refrigeration legend furnished by the store.

Install 

P-traps

 (oil traps) at the base of all suction line vertical

risers.

Pressure drop

 can rob the system of capacity. To keep the

pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only.

CONTROL SETTINGS

See the “Case Specs” section of this guidebook for the
appropriate settings for your merchandiser. Maintain these
parameters to achieve near constant product
temperatures. Product temperature should first be
measured in the morning, after having been refrigerated
overnight. For all multiplexing, defrost should be time
terminated. Defrost length and frequency should as
directed in the Case Specifications section of this guide.
The number of defrosts per day should never change. The
duration of the defrost cycle may be adjusted to meet
conditions present at your location.

Содержание ASCS

Страница 1: ...Chino ASCS DELI MEAT FISH SERVICE CASE REV 0303 Installation Operation Manual ASCS DELI MEAT FISH SERVICE CASE P N IGSV ASCS 0303 INSTALLATION OPERATION GUIDE...

Страница 2: ...exist and is found to be the responsibility of Hussmann Chino notify Hussmann Chino If such a shortage involves the carrier notify the carrier immediately and request an inspection Hussmann Chino will...

Страница 3: ...nent position as possible Keep in place attached case until ready to set bolt to adjoining case TIGHTEN GLASS SCREWS Tighten screws along clamshell located on the underside of glass before placing uni...

Страница 4: ...hinge operation and glass alignment problems NOTE A To avoid removing concrete flooring begin lineup leveling from the highest point of the store floor B When wedges are involved in a lineup set them...

Страница 5: ...e adjoining case is a hot case the cases are bolted together by mans of a bracket located behind the front panel Remove the front panel by lifting it up and out COMMON END BETWEEN UNLIKE CASES AND HOT...

Страница 6: ...ff the center of the case to allow use of the P trap pipe section Never use two water seals in series in any one line Double P traps in series will cause a lock and prevent draining 3 Always provide a...

Страница 7: ...light savings time Military time 24 hr clock or 12 hour clock may be selected by pressing and holding the h key while depressing the h key A flashing light indicated a missing selection in the program...

Страница 8: ...NLESS 225 01 0603 COMPRESSION FITTING PVC 1 2 OD x 1 2 NPT 225 01 1322 SOLENOID VALVE ALCO 222CB B B AMS 225 01 1340 UNION TEE COMPRESSION PVC 1 2 OD x 1 2 OD 225 01 1324 COMPRESSION FITTING PVC 1 2 O...

Страница 9: ...energy consumption Set defrost cycles as listed in the Case Specifications Data for your particular case The number of defrosts per day should never change The duration of the defrost cycle may be adj...

Страница 10: ...REAR INTERIOR WALL OF CASE VIEWED FROM FRONT BALL VALVE HAMMON 225 01 2026 1 4 100 X 1 8FPT SW ADAPTER 225 01 2089A 1 4 OD X 1 8 FPT SW ADAPTER 225 01 3059 1 8 MPT X 1 4 COMP PVC ADAPTER 225 01 3059...

Страница 11: ...valves are furnished as standard equipment unless otherwise specified by customer EXPANSION VALVE ADJUSTMENT Expansion valves must be adjusted to fully feed the evaporator Before attempting any adjus...

Страница 12: ...r external appliances BEFORE SERVICING Always Disconnect Electrical Power at the Main Disconnect when servicing or replacing any electrical component This includes but not limited to Fans Heaters Ther...

Страница 13: ...dges of the bumper must be firmly seated into the retainer by applying with a rubber mallet not by hand 7 The bumper should be struck by the mallet at a slight angle that forces the bumper back into i...

Страница 14: ...tic as it does not allow for proper circulation Make sure the cloth or paper is in direct contact with the product 10 Turn and rotate the meat fairly often The blood which gives the pink color works i...

Страница 15: ...ial coatings on the glass surface itself To preserve this coating and the optical clarity keep the glass clean Windex or Glass Plus are the only solutions recommended for use in cleaning non glare gla...

Страница 16: ...an blades with the raised embossed side of the blade TOWARD THE MOTOR COPPER COILS The copper coils used in Hussmann merchandisers may be repaired in the field Materials are available from local refri...

Страница 17: ...tled lubricant in the cylinders and prevent any stress on the front glass 1 3 RE ADJUSTMENT After Initial STARTUP In addition to verifying that theAllen screws on the lift up glass are tightened when...

Страница 18: ...Back of Case Inside of Case Chrome cap for access to nut plate nut plate CUT VIEW Mini Top Hardware Adjust glass Up and Down vertically Adjust glass Side to Side horizontally Adjust glass Front to Ba...

Страница 19: ...0 Out 1 208 13 0 Meat Fish 33 26 26 26 Air Evap fans 8 x 15 3 4 3 36 50 In 230 Humidity 3 1 4 Axial 2 NOTE Case temperature is controlled by a factory installed thermostat and suction solenoid excludi...

Страница 20: ...04 0111 125 04 0112 125 01 0110 SUCTION SOLENOID HUMIDITY FAN 125 04 0110 BALLAST LH3 120 L 1 125 04 0142 THERMOSTAT DUPLEX RECEPTACLES NOT USED GFCI DEDICATED LINE 125 04 0113 NOT USED 125 04 0113 N...

Страница 21: ...0110 SUCTION SOLENOID HUMIDITY FAN 125 04 0110 BALLAST LH3 120 L 2 125 04 0142 THERMOSTAT DUPLEX RECEPTACLES NOT USED GFCI DEDICATED LINE 125 04 0113 NOT USED 125 04 0113 NOT USED 125 04 0100 SINGLE...

Страница 22: ...SWEEP HEATER OPTIONAL HEATER SWITCH OPTIONAL 125 04 0115 125 04 0115 AIR SWEEP ANTI SWEAT FANS 125 04 0121 LEDGE LIGHT OPTIONAL SEE DWG W0100016 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 EVAPORATOR...

Страница 23: ...EP HEATER OPTIONAL HEATER SWITCH OPTIONAL 125 04 0115 125 04 0115 AIR SWEEP ANTI SWEAT FANS 125 04 0121 LEDGE LIGHT OPTIONAL SEE DWG W0100016 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 EVAPORATOR FAN...

Страница 24: ...15 125 04 0115 AIR SWEEP ANTI SWEAT FANS 125 04 0121 LEDGE LIGHT OPTIONAL SEE DWG W0100016 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 EVAPORATOR FAN CAP BA...

Страница 25: ...L 125 04 0115 125 04 0115 AIR SWEEP ANTI SWEAT FANS 125 04 0121 LEDGE LIGHT OPTIONAL SEE DWG W0100016 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 EVAPORATOR...

Страница 26: ...R WEDGE FAN 3 AXIAL FAN WEDGE FAN HARNESS 125 04 0124 EVAPORATOR FAN PLENUM EXTENSION 125 04 0148 IF REQUIRED EVAPORATOR FAN PRIMARY FAN HARNESS 125 04 0147 CABLE SPLITTER 125 04 0119 USE AIR SWEEP HA...

Страница 27: ...L CASE WATER FLUSH SYSTEM REDRAWN TO SPEC FROM 10 21 99 BY AEC 04 15 02 AEC M 5 4 3 2 1 12 00 5 4 3 2 1 GR SSLIN TIME CLOCK 125 04 0100 125 04 0119 PRIMARY FAN HARNESS EVAPORATOR FAN 125 04 0127A SOLE...

Страница 28: ...8T5 830 FP28T5 830 FP28T5 830 FP2IT5 830 FP2IT5 830 CAP UNUSED RED LEAD CAP UNUSED RED LEAD 4 CASES 6 CASES 8 CASES 10 CASES 12 CASES RED YELLOW YELLOW RED RED YELLOW RED RED 125 04 0119 BALLAST FULHA...

Страница 29: ...USE 1 2 3 WHITE DEDICATED GFCI 4 5 6 YELLOW RECEPTACLES 7 10 ORANGE LIGHTS 8 11 PURPLE ANTI SWEAT HTR FAN 9 12 BROWN EVAP FANS T STAT 1 2 3 4 5 6 7 8 9 10 11 12 B B B W G 3 2 1 3 2 1 3 2 1 3 2 1 3 2...

Страница 30: ...LOR USE 1 2 3 WHITE DEDICATED GFCI 4 5 6 YELLOW RECEPTACLES 7 10 ORANGE LIGHTS 8 11 PURPLE ANTI SWEAT HTR FAN 9 12 BROWN EVAP FANS T STAT 1 2 3 4 5 6 7 8 9 10 11 12 B B B W G 3 2 1 3 2 1 3 2 1 3 2 1 3...

Страница 31: ...used Not used 125 04 0117 125 04 0115 Anti sweat Fans Optional 125 04 0115 125 04 0115 125 04 0119 Heater Wire case rear Tubular Heater Element Front air sweep heater Optional 125 04 0122 125 04 0123...

Страница 32: ...00 Not used Not used 125 04 0115 Anti sweat Fans Optional 125 04 0115 125 04 0115 125 04 0119 Heater Wire case rear Tubular Heater Element Front air sweep heater Optional 475 01 1421 2 Anti sweat Heat...

Страница 33: ...25 04 0112 125 04 0113 125 04 0113 125 04 0112 125 04 0110 125 04 0100 125 04 0121 125 04 0115 125 04 0115 125 04 0115 125 04 0119 Heater Wire case rear Tubular Heater Element Front air sweep heater O...

Страница 34: ...12 125 04 0113 125 04 0113 125 04 0112 125 04 0110 125 04 0100 125 04 0115 Heater Wire case rear Anti sweat Fans Optional 125 04 0121 125 04 0115 Tubular Heater Element Front air sweep heater Optional...

Страница 35: ...n s recommendations b Observation of outside influences such as drafts radiant heating from the ceiling and from lamps Such influence should be properly corrected or compensated for c At the same time...

Страница 36: ...t been modified to use replacements for CFC 12 CFC 502 or other refrigerant If so have the modifications been made in accordance with the recommendations of Hussmann equipment Is the refrigerator char...

Страница 37: ...omes in contact with the tool or equipment i Make sure that all refrigeration equipment is installed and adjusted in strict accordance with Hussmann s recommendations j See that all storage and refrig...

Страница 38: ...IGSV ASCS 0303 38...

Страница 39: ...tion under this warranty shall be limited to a period not to exceed five years from date of factory shipment On Hussmann refrigeration systems an additional 4 year extended warranty for the motor comp...

Страница 40: ...ticular unit They can be found on a small metal plate on the unit Please note them below for future reference MODEL SERIAL NUMBER Chino Additional copies of thispublication may be obtained by contacti...

Отзывы: