UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
5 Operations
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
139
Step 2
On the
Monitoring
>
Control
>
System Commands and Tests
page, click
Start
next to
Forced equalized charging
to start a forced equalized charging test.
Figure 5-9
Starting a forced equalized charging test
Click
Stop
next to
Forced equalized charging
in any of the following cases:
The forced equalized charging test duration reaches the forced equalized charging protection time
(12–24 h, 18 h by default).
The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
An alarm is generated.
----End
5.1.6.2 Shallow Discharge Test
Before conducting a shallow discharge test, check whether the requirements of a shallow
discharge test are met. If the requirements are met, the button for starting a shallow discharge
test is available. Otherwise, the button is unavailable.
Before a shallow discharge test, ensure that:
The UPS works in normal mode with a load ratio fluctuation less than 10%.
The UPS has generated no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
Automatic Shallow Discharge Test
Step 1
Log in to the WebUI.
Step 2
On the home screen of the WEBUI, choose
Monitoring
>
Param. Settings
>
Battery
Param.
, and set
Sched. shallow dis. test
to
Enable
.