UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
3 Installation
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
47
Figure 3-5
Removing L-shaped brackets
Properly store the removed L-shaped brackets and screws, which can be used to secure the UPS in the
future.
Step 9
Push the cabinet along the sliding plate and move the cabinet over its castors to a position
near the installation position.
----End
3.2 Installing a Single UPS
3.2.1 Installing the UPS
Supporting the UPS with Leveling Feet
Step 1
Lower the four leveling feet at the bottom of the UPS using a wrench until all the four castors
at the bottom hang in the air and the leveling feet bear the whole cabinet weight.