8 Technical Specifications
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
160
Item
Specifications
2.23–2.30 V/cell. The default voltage is 2.25 V/cell (30–44
batteries).
Minimum cell voltage
1.6–1.9 V/cell
Table 8-7
Output electrical specifications
Item
Specifications
System
Three-phase, four-wire, and PE
Voltage
380 V AC/400 V AC/415 V AC (line voltage)
Frequency
In normal mode, the frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50/60 Hz with a tolerance
of ±0.05%.
THDv
THDv ≤ 1% (full linear load)
THDv ≤ 4% (full non-linear load)
Power factor
1
Transfer time
Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Output voltage imbalance
Voltage imbalance: ±3%; phase imbalance: ±2°
Overload capability
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60
minutes
110% < load ≤ 125%: transfer to bypass mode after 10
minutes
125% < load ≤ 150%: transfer to bypass mode after 1
minute
Load > 150% or a short circuit occurs: run for 200 ms
Table 8-8
System electrical specifications
Item
Specifications
Parallel reliability
Redundant parallel signals
Parallel ECO function
Supported