UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
95
Bypass Settings
Figure 4-18
Bypass Settings Screen
Item
Description
Default Value Value Range
Max. voltage
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
When the voltage level is 380 V,
the value range is +10%, +15%,
+20%, and +25%. The default
value is +15%.
When the voltage level is 400 V,
the value range is +10%, +15%,
and +20%. The default value is
+15%.
When the voltage level is 415 V,
the value range is +10% and
+15%. The default value is
+10%.
Min. voltage
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
–20%
–10%, –20%,
–30%, –40%,
–50%, –60%
Frequency
range
When the difference between the
bypass input frequency and the
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable.
±2 Hz
±0.5 Hz to ±6
Hz
Battery Settings
Battery parameter settings greatly affect battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following: