Monitoring
Parameter
Displayed
on the Host
Device
Port
Application in
the F01D200
Cabinet
Application in
the F01D500
Cabinet
Application in
the F01D1000
Cabinet
Wiring alarm
JTP1
MDF
MDF
MDF
Battery Tem
VBTEM2
Battery
temperature
sensor
Battery
temperature sensor
Battery
temperature sensor
environment
Tem/
environment
Hum
VTEM2
Temperature and
humidity sensor
Temperature and
humidity sensor
Temperature and
humidity sensor
NOTE
Before adding a user-defined analog or monitoring digital parameter, make sure that the port corresponding
to this parameter is properly connected to an environment monitoring cable.
Data Plan
provides the data plan for configuring the monitoring parameters of the ETP4890.
Table 8-14
Data plan for configuring the monitoring parameters of the ETP4890
Item
Data Plan for the
F01D500 Cabinet
Remarks
EMU
Type: POWER4875L
During the configuration of the ETP4890, the type
of the ETP4890 is selected as
POWER4875L
.
SN: 0
-
Subnode ID: 0
The subnode ID must be the same as the subnode
setting of the corresponding DIP switches on the
EMU, but the subnode ID must be different from
IDs of the other subnodes on the same bus.
Charging
parameters
of the battery
Charging mode of the
battery: automatic
This parameter is set according to the actual
requirements.
automatic: The power system automatically
adjusts the charging mode of batteries according
to the status of the battery set.
equalizing: The battery is charged forcibly so as
to quickly compensate for the lost capacity of the
battery.
floating: The battery adjusts charging/
discharging when it is in saturation.
Default: automatic.
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
139