l
Configure the humidity parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power environment humidity
command.
12. Configure the extended digital parameters.
huawei(config-if-power4845-0)#
power outside_digital 1 available-level low-
level name Fan
huawei(config-if-power4845-0)#
power outside_digital 3 available-level low-
level name SPD
13. Query the configuration.
huawei(config-if-power4845-0)#
display power system parameter
EMU ID: 0 Power system information
----------------------------------------------------------------------------
charge control state : automatic control
equalizing Voltage : 56.500V floating Voltage: 53.500V
charge lmt quotiety: 0.150 equalizing time : 60 days
battery number : 1
battery 0 capacity : 75 AH
battery Temperature Upper : 80 C battery Temperature Lower : -20 C
Temp redeem quotiety: 80mV
load off permit : forbid load off voltage : 44.000V
battery off permit : permit battery off voltage : 43.000V
shunt quotiety : 100A
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 2
module 0 address : 1 module 0 control state: On
module 1 address : 2 module 1 control state: On
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 70
Battery high-temperature-off permit: permit
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4845-0)#
display power environment parameter
EMU ID: 0 power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestHigh TestLow Unit type
0 Temperature 68 -5 80 -20 C
Current
1 Humidity 80 10 100 0 %R.H.
Current
----------------------------------------------------------------------------
DigitalID Name Available Level|DigitalID Name Available Level
0 - 1 | 1 Fan 0
2 - 1 | 3 SPD 0
4 - 1 | 5 - 1
6 - 1
----------------------------------------------------------------------------
14. Query the alarm information, and confirm that the door status alarm other than alarms for
other monitoring parameters is generated.
huawei(config-if-power4845-0)#
display power alarm
EMU ID: 0 Power alarm information
--------------------------------------------------------------------
mains supply yes : yes mains supply lack : normal
total vol lack : normal
load fuse 0 : connect second fuse : connect
load off : on battery off : on
battery 1 loop : connect
environment Temperature : Normal environment Humidity : Normal
door alarm : Alarm water alarm : Normal
fog alarm : Normal
module 0 : normal
UA5000 Universal Access Unit
Environment Monitoring
6 EPS30-4815AF Monitoring Solution
Issue 01 (2012-08-17)